Delta DVP06XA-S
Delta DVP06XA-S is a mixed analog I/O expansion for a compatible DVP Slim PLC CPU, with 4 analog inputs and 2 analog outputs. CH1–CH4 read field signals and CH5–CH6 generate voltage or current references. This DVP Slim analog module can read a pressure transmitter and supply a reference to an AC drive.
Input and output ratings
Inputs CH1–CH4. Voltage input ±10 V, 12 bits, 5 mV/LSB and 200 kΩ. Current input ±20 mA, 11 bits, 20 µA/LSB and 250 Ω. Full bipolar modes give raw values of −2000 to +2000 for voltage and −1000 to +1000 for current. Select each analog input mode in CR#1.
Outputs CH5–CH6. 0–10 V or 0–20 mA, 12 bits. The basic digital-to-analog conversion modes use commands from 0 to 4000. Step size is 2.5 mV or 5 µA. Use a load of at least 1 kΩ for voltage output or at most 500 Ω for current output.
The sheet specifies 3 ms × channel count response time and ±0.5% of full scale accuracy at 25 °C. Use an external 24 V DC DIN rail power supply. The permitted range is 20.4–28.8 V DC and maximum consumption is 2 W. Mount the module on 35 mm DIN rail. Route analog wiring away from motor and power wiring inside the control panel.
4–20 mA scaling and the S / S2 difference
For voltage input, use V+ and COM. For current input, bridge V+ to I+ on that channel and follow the I+/COM loop diagram. For output, use V+/COM for voltage or I+/COM for current. Check the analog sensor’s supply and 0–10 V or 4–20 mA signal type first.
4–20 mA example. With the factory curve in input mode 2, 4 mA reads approximately 0 and 20 mA reads approximately 1000. In output mode 2, command 0 gives 4 mA and command 4000 gives 20 mA. Scale 0–10 V and 4–20 mA signals using the actual channel mode and calibration.
DVP06XA-S uses a common COM. The model shares an analog and digital ground without galvanic isolation between those circuits. DVP06XA-S2 has separate COM1–COM4 input terminals and voltage input impedance of at least 1 MΩ. An optocoupler isolates its analog circuit from the digital circuit. Delta shows the same output wiring for both models. Check the appropriate input diagram before replacement.
Programming, channel registers and RS-485
Edit the project for the compatible Delta PLC host using WPLSoft or a CPU-compatible release of ISPSoft. Check COMMGR for ISPSoft. Connect the programming cable to the CPU. Delta lists UC-PRG020-12A for suitable 8-pin mini-DIN RS-232 ports. Choose any USB or serial adapter to match the host port.
FROM/TO registers. CR#0 identifies the module as H’CC for the S version. CR#1 sets channel modes. CR#6–9 hold averages and CR#12–15 hold present inputs. CR#10 commands CH5 and CR#11 commands CH6. CR#30 holds error status. If the first special module is K0, FROM K0 K12 D100 K4 reads four present inputs into D100–D103. Check the actual module order. Use scaled engineering values for HMI or SCADA displays.
CRs are also accessible via the module’s RS-485 port. CR#31 sets the station and CR#32 sets the serial format. The sheet lists a factory default of station 1, ASCII 9600 7E1. When selecting Modbus RTU, check frame restrictions on S firmware V4.12 and earlier. For example, the CH1 present value has protocol address H’40D4. Check whether your software expects a zero-based address or a one-based register number.
Related modules and field checks
For input-only expansion, see DVP04AD-S, DVP06AD-S and DVP04AD-S2. Output-only options include DVP02DA-S, DVP04DA-S and DVP04DA-S2. DVP04AD-SL and DVP04DA-SL use a different expansion arrangement. Confirm the host’s expansion side and analog module channel type before selection.
Editor’s Note
Start with the full label on a used unit. S and S2 look similar at the terminal strip. Check the input common layout and the model value in CR#0.
If a current input stays at zero, inspect that channel’s V+/I+ bridge and loop supply. A missing bridge affects the measurement even with the correct mode.
Apply at least two calibrated input points. Check the raw value in CR#12–15, then compare it with the scaled value in the PLC.
Disconnect the output from the machine and measure it with a suitable test load. If current loop resistance exceeds 500 Ω, correct the load first.
If all channels drift, check the external 24 V and the common reference. Ask for separate test results for all four inputs and both outputs before buying.
PDF manuals and technical documents
See the Delta DVP PLC files page for the joint S/S2 instruction sheet DVP-0010430-01. The DVP06XA-S terminal drawing is on PDF page 2, the CR table on pages 4–5 and the conversion curves on page 6.
DVP06XA-S main page · Slim analog modules · DVP expansion modules · DVP PLC series · Delta PLC · Used Delta models · Delta manuals
External references
Delta DVP06XA-S / S2 instruction sheet · Delta S and S2 comparison bulletin