Delta DVP Slim load cell modules
Delta DVP Slim load cell modules
Delta DVP Slim load cell modules convert the millivolt bridge signal from 4- or 6-wire load cells into weight data. With a compatible PLC, they can handle hopper and silo weighing, bag filling, batching and conveyor checkweighing. The range includes five single- and dual-channel models. Choose the module by counting the independent weighing points and checking the required update time and weight-controlled outputs.
Model selection and specifications
| Model | Weighing channels | ADC | Application |
|---|---|---|---|
| DVP01LC-SL | 1 | 20 bit | One platform or hopper |
| DVP02LC-SL | 2 | 20 bit | Two independent weighing points |
| DVP201LC-SL | 1 | 24 bit | Single-channel dosing or dynamic weighing |
| DVP202LC-SL | 2 | 24 bit | Two filling heads or two separate scales |
| DVP211LC-SL | 1 | 24 bit | Systems requiring 2 digital inputs, 4 NPN outputs and 1 current output |
The 01/02LC-SL models have selectable ranges of 0–1, 0–2, 0–4 and 0–6 mV/V and response settings of 2, 10, 20, 40, 80, 200 and 380 ms per channel. The 201/202/211LC-SL models add 0–20, 0–40 and 0–80 mV/V ranges and have selectable response settings from 2.5 to 400 ms per channel. The table gives the ADC resolution. The smallest repeatable weight change depends on the sensor, mounting, wiring and filter settings.
DVP02LC-SL document discrepancy. The table follows the 20-bit ADC specification in the 2026 module manual. The 2010 DVP02LC-SL instruction sheet lists 24-bit internal resolution. If resolution is critical to a replacement, confirm the hardware revision with Delta.
The DVP211LC-SL can use its own NPN outputs to control coarse and fine filling at weight thresholds. Its 0–20 mA or 4–20 mA current output can be scaled to weight. If the machine needs other analog or digital signals, check the CPU and field I/O requirements alongside the DVP Slim analog modules.
CPU compatibility and left-side expansion
All five models attach to the left-side expansion bus of a supported CPU. Delta lists DVP-SA2, DVP-SX2 and CPUs in the SV family as examples. For a DVP-SV2 or an L-suffix CPU, confirm the exact part number, left-side support, module limit and applicable versions in the CPU hardware manual. Delta also lists all five modules in its SV3/SX3 hardware manual. On supported DVP systems, left-side module positions run from 100 to 107, starting next to the CPU. The PLC reads and writes module registers using FROM/TO instructions. Check the module number in the Ladder program when moving a module.
Load cell wiring and mV/V settings
The module uses a 24 V DC supply and provides nominal 5 V DC excitation to the strain-gauge load cell. In the Wheatstone bridge circuit, EXC± provides excitation, SIG± carries the signal and SEN± senses the voltage at the bridge. With a 4-wire cell, link EXC+ to SEN+ and EXC− to SEN− at the module. A 6-wire cell has separate sense leads. Check the wire colours against the sensor datasheet and follow Delta’s diagram for the shield and cabinet grounding.
A 2 mV/V cell on 5 V excitation produces about 10 mV of signal change at rated load. Set the channel sensitivity from the nameplate. See how load cells work, load cell types and weighing sensor selection for more on the sensor, mounting and capacity.
Four load cells under one platform can feed a junction box and be read as one channel. Use two independent channels to read two scales or filling heads separately. For parallel cells, check the combined bridge resistance, total excitation current and corner balancing.
LCSoft, PLC software and cables
LCSoft is used to monitor weight, read settings, zero and tare the scale, and adjust filtering and calibration. For a direct PC connection, use the module’s COM1 RS-232 port and a cable wired to Delta’s pinout. For a USB PC, install the driver for the USB-to-RS-232 adapter and select the COM port assigned by Windows in LCSoft. On COM2 RS-485, match the station address, baud rate, data bits, parity, stop bits and Modbus ASCII or RTU mode at both ends. The serial interface can read module data independently of the PLC’s left-side bus.
For PLC programming, choose the WPLSoft or ISPSoft version supported by the CPU. Set up the ISPSoft connection in COMMGR. For the DVP12SA211R with mini-DIN COM1 RS-232, Delta lists the UC-PRG020-12A cable. The SV3/SX3 manual lists ISPSoft and DIADesigner. These CPUs can also connect to a PC over USB. Check the CPU and weighing module ports separately against the Delta DVP programming cables page and the wiring diagrams. See the industrial communications guide for serial network basics.
Zero, tare and calibration
1. Zero the empty platform. Correct binding and any load applied by attached pipes or cables. Record the empty reading once the measurement is stable.
2. Apply a reference weight. Use a known load at a suitable point in the working range. Calibrate each channel separately on a dual-channel module. If zero plus one reference load is insufficient, Delta documents up to 20 calibration points on the 201/202/211 family.
3. Check gross and net. Subtract the container tare from the gross reading to obtain net weight. Once calibrated and tared, check repeatability with several weights. 4. Save and verify. Store the settings in the module and verify zero and the reference load again after a power cycle. See weight measurement and the weighing FAQ for additional checks.
Troubleshooting a missing weight reading
Find where the reading disappears. If LCSoft also shows no weight, check the 24 V supply, EXC/SEN wiring and channel sensitivity. If LCSoft shows the correct weight, check the PLC’s left-side module number or serial settings. Decode CR#51 using the table for your module. On 201/202/211 models, for example, the no-load and stable-reading bits indicate normal operating states.
Editor’s Note
When buying used, ask for close-up photos of the full model label, left-side bus connector and terminals. For a dual-channel module, ask to see a zero and reference-load reading on each channel.
If the empty scale drifts, first look for uneven feet, a pipe pulling on the hopper, or a snagged cable. Filtering can hide a mechanical problem that returns during production.
If the reading fluctuates only while the motor runs, inspect the variable-frequency drive output cable, the sensor cable route and sources of electromagnetic interference. Find the source of the noise before adjusting zero.
A stronger filter can steady the display and delay valve shutoff. Measure the difference between target and final weight during both bench testing and actual filling cycles.
Before replacing the module, record channel sensitivity, serial parameters, tare and limits. For the final check, use a reference weight to confirm the PLC and HMI use the same unit and decimal scale.
Related Delta topics and PDF files
Delta DVP PLC PDF files · Delta DVP expansion modules · Delta DVP PLC series · Delta LCSoft
OtomasyonAVM PDFs · Installation and wiring sheet for all five models (2023, EN/TR) · DVP201/202/211LC-SL operation manual (2022, EN)
External references
Delta DVP module manual, Chapter 12 (2026, EN) · DVP201/202/211LC-SL operation manual (2019, EN) · Delta PLC/HMI Cable Selection Guide (EN) · Delta SV3/SX3 hardware manual, §1.1.2 (EN)