Delta DVP211LC-SL
Delta DVP211LC-SL – Single-Channel Load Cell and Weighing Control Module
The Delta DVP211LC-SL is a Delta DVP module with one load cell measurement channel, two digital inputs, four transistor outputs and one analog current output. It fits the left-side expansion bus of a compatible CPU and can also operate independently through its own RS-485 interface. Typical uses include tank weighing, filling and weight threshold monitoring with a load cell.
Power supply, signal range and response time
The module uses a 24 V DC supply with a static operating range of 20.4–28.8 V DC. It supplies nominal 5 V DC excitation to the load cell. The measurement ADC is 24 bit and the PLC weight data is transferred as a 32-bit value. Select 1, 2, 4, 6, 20, 40 or 80 mV/V to match the sensor. Measurement response time is adjustable in steps from 2.5 to 400 ms.
A strain-gauge load cell’s mV/V rating describes its output at rated load per volt of excitation. For example, a 2 mV/V cell produces approximately 10 mV at rated load with 5 V excitation. Use shielded cable for this small analog signal and route it separately from motor cables. If the reading fluctuates while a drive is running, check shield termination, grounding and potential sources of electromagnetic interference.
4-wire and 6-wire load cell connections
EXC+/EXC− supply bridge excitation, SIG+/SIG− carry the measurement signal, SEN+/SEN− sense excitation at the load cell and SHD is the cable shield terminal. For a 4-wire cell, jumper EXC+ to SEN+ and EXC− to SEN− at the module. For a 6-wire cell, connect the separate sense wires to their respective SEN terminals. Use the sensor’s wiring sheet to identify each wire and its polarity.
Digital inputs, transistor outputs and analog current
X0 and X1 are 24 V DC inputs with a shared S/S terminal. Select the S/S polarity for the connected NPN or PNP sensor. Inputs can be assigned to functions such as zero or tare. For Y0–Y3, Delta shows NPN output wiring with UP at +24 V and ZP at 0 V. The outputs can report conditions such as a weight threshold or a stable reading, depending on the configuration.
AO+/AO− is the current output. Use CR#103 to select 0–20 mA or 4–20 mA and choose the output source. The output can follow a digital command in CR#100 or the module’s scaled weight value. Set the receiving device’s current input to the same range.
LCSoft calibration and weight data
Use LCSoft to configure and calibrate the module. For two-point calibration, first capture zero with the platform empty. Then apply a known reference weight and enter its corresponding digital value. For example, enter 1000 for 1 kg when the PLC uses grams. After calibration, recheck the empty platform and the known load. Delta documents calibration with up to 20 points.
Use FROM/TO in the PLC program to access the module’s registers. In a compatible left-side expansion arrangement, module numbers run from 100 to 107, starting closest to the CPU. CR#2 sets sensor sensitivity and CR#3 sets measurement response time. The weight’s low word is in CR#12 and its high word is in CR#13. Read the two words as one 32-bit value. CR#51 reports measurement and diagnostic status bits.
CPU programming software and cable
Download the program to the host CPU using a supported version of WPLSoft or ISPSoft. Configure the ISPSoft connection through COMMGR. For example, use the UC-PRG015-01A with the DVP-SX2 mini-USB port or the UC-PRG020-12A with a compatible COM1 RS-232 port. When selecting a DVP-SA2 or another CPU, verify left-side expansion support for the exact model. For direct LCSoft setup, use the module’s compatible serial interface.
Editor’s Note
When buying a used unit, check the DVP211LC-SL label, measurement terminals, left-side expansion socket and AO terminals.
If the reading stays at one extreme, use a multimeter to check excitation at the EXC terminals. For a four-wire sensor, also verify the SEN jumpers.
If the reading moves in the opposite direction as weight increases, check SIG polarity against the sensor’s wiring sheet.
If the reading fluctuates during filling, inspect mechanical vibration, cable routing and shield termination before changing filters. Recheck response time after adjusting the filter.
After calibration, verify the reading with an intermediate reference load. If the analog output is in use, also measure the current at the receiver at the low and high weighing points.
Related models and topics
The DVP201LC-SL and DVP202LC-SL are 24-bit models with one and two weighing channels respectively. The DVP01LC-SL and DVP02LC-SL are 20-bit models with one and two channels respectively. For sensor basics, see how a load cell works.
Manual and wiring diagram
Chapter 12 of the DVP Series Module Manual covers the terminal diagrams, control registers and calibration examples. See Delta DVP PLC files for the series documentation.
DVP211LC-SL · DVP Slim load cell modules · Used Delta PLC models · Delta Automation