Delta DVP16XN211T – 16 Transistor Output PLC Expansion Module

Delta DVP16XN211T belongs to the DVP ES2/EX2 expansion module family. It adds 16 sinking (NPN) digital outputs to a host PLC and has zero inputs. Its 5–30 V DC load circuit can switch suitable indicator lights and DC interface inputs under host PLC control.

Output ratings and terminal wiring

Delta’s model wiring section specifies 0.3 A per output and 1.2 A per common. The general table in the 2009 DIDO sheet lists 0.5 A per output and 4 A per common. Use the 0.3 A and 1.2 A limits until the rating for the device revision has been verified. For example, eight 0.2 A loads running together draw 1.6 A and exceed the 1.2 A group limit.

UP0/ZP0 serve Y0–Y7 and UP1/ZP1 serve Y10–Y17. Each UP/ZP pair requires an external 24 V DC auxiliary supply. The manufacturer drawing shows UP at +24 V and ZP at 0 V. In a circuit using the same 24 V supply, connect each load between +24 V and its Y terminal. When the output turns on, current returns to 0 V through ZP. Connect the marked protective earth terminal to ground and leave NC unconnected.

The manual’s output table lists 50 µs turn-on, 200 µs turn-off and a maximum switching rate of 100 Hz. The PLC scan also affects the rate in service. The table gives no direct inductive-load rating, so select a suitable interface for coil loads.

Host PLC, Y addresses and programming

Use this right-side expansion module with supported DVP-ES2 and DVP-EX2 CPUs. Delta’s DVP-ES3 hardware manual also lists the model. Check the exact host code and expansion limit. As the first digital expansion on a DVP32ES200T, the expected range is Y20–Y37. Local Y0 maps to project address Y20 and local Y10 maps to Y30. Addresses are octal and preceding output modules can change the starting address.

The program runs on the host PLC. Use WPLSoft or ISPSoft according to the ES2/EX2 CPU and project version. For ISPSoft, select the correct COM port in COMMGR. Delta’s cable guide lists the UC-PRG020-12A USB programming cable for COM1/RS-232 on the CPU. The UC-MS020-01A connects through a PC serial port or a suitable USB-to-RS-232 adapter. Install the appropriate driver for the USB connection and select its COM number. See DVP programming cables for additional cable options.

Related models

DVP16XN211R has 16 relay outputs. DVP08XN211T offers eight transistor outputs, DVP16XP211T combines eight inputs with eight transistor outputs, and the AC-powered DVP24XN200T offers 24 transistor outputs. Compare the supply, expansion connector and terminal drawing before replacing a legacy ES/EX DVP16XN11T.

Editor’s Note

Read the 211T suffix and identify both UP/ZP pairs. Photograph the wiring before removing the terminal block.

If the output LED lights and the load stays off, measure the group’s 24 V supply across UP and ZP.

When a whole group fails, check the common return and wiring. For an individual fault, compare the channel with a working one.

Test all 16 channels individually using a suitable low-current resistive load on a bench isolated from the machine.

For used units, ask for clear label and terminal photos plus the results of loaded tests on both groups.

PDF documents

See Delta DVP PLC PDF files for the series documents. Page 2-13 of the module manual shows the DVP16XN211T wiring. Page 1-3 of the cable guide shows the PC connection for the host PLC.

Related topics

For input expansion, see DVP08XM211N and DVP16XM211N. The Delta PLC software section covers programming and communication tools.

Navigation · Delta · Delta PLC · DVP PLC series · ES2/EX2 modules · PDF files

External references

Delta DVP Series Module Manual · Delta DVP-ES2 DIDO Instruction Sheet · Delta PLC/HMI Cable Selection Guide · Delta WPLSoft / ISPSoft