Delta AH10PFBS-5A
Delta AH10PFBS-5A PROFIBUS-DP slave communication module
The Delta AH10PFBS-5A is a communication module that connects a Delta AH500 PLC to a PROFIBUS-DP network as a slave station. It exchanges cyclic data with a DP master. For example, a Siemens S7-300 acting as master can exchange status and command data through the AH500’s D registers.
Installation. The module fits an I/O slot on the AH500 main rack and receives 5 V DC from the backplane. The AH10PFBM-5A is the DP master module. The AHRTU-PFBS-5A is a PROFIBUS-DP remote I/O station. See AH expansion modules and AH power supplies for system layout.
DB9 wiring and station address
The port uses RS-485 over shielded twisted-pair cable and detects the bus rate automatically up to 12 Mbit/s. On the DB9 connector, pin 3 = B (P/+), pin 8 = A (N/−), pin 5 = DGND and pin 6 = VP (+5 V). See the PROFIBUS FAQ for network wiring and termination.
The valid station address range is 1–125. The two front rotary switches use hexadecimal notation. For 26 = 1A, set the high digit to 1 and the low digit to A. The new address takes effect after a power cycle.
GSD file, ISPSoft and data mapping
Import DELA0AFE.GSD into the DP master’s configuration software. Configure the station with ID 0x0AFE using the address selected on the rotary switches. In Delta ISPSoft, check the module’s main-rack slot in HWCONFIG. See Delta GSD files and device description files for file types.
The module supports up to 100 input words and 100 output words of cyclic data. In the master project, In is data the master reads from the AH500 and Out is data the master writes to it. Verify the starting AH500 D register for each data block in the project.
Manual and PDF
Delta AH500 Module Manual (English PDF) · Chapter 13 starts on PDF page 621. It covers DB9 wiring, the GSD file, data mapping and an ISPSoft example. For other series documents, see Delta AH PLC PDF files.
Editor’s Note
When buying a used unit, first check that the nameplate reads AH10PFBS-5A.
Inspect the DB9 pins, connector screws and both address switches.
On the bench, exchange a small block of data in both directions with a DP master.
If NET is red or the display shows F6, check the cable, station address and the master’s GSD definition.
Before replacing a card, record the working address, data lengths and D-register mappings.
Related topics
Other communication modules include AH10DNET-5A, AH10COPM-5A, AH15EN-5A, AH10SCM-5A and AH15SCM-5A. See industrial communication for network options.
Delta PLC accessories · Delta PLC software · Delta PLC · Second-hand Delta products
External references · Delta AH500 Module Manual · Delta AH500 Hardware and Operation Manual