6ES5 951-7ND31

Siemens 6ES5 951-7ND31 SIMATIC S5 power supply

The 6ES5 951-7ND31 is an isolated PS 951 power supply used in SIMATIC S5-115U, S5-115H and documented S5-115F installations. It takes 24 V DC and supplies 5 V DC ±2% to the S5 rack backplane. The front panel is marked 7/15 A. Siemens specifies 7 A maximum for the fanless S5-115F. The 15 A rating in S5-115U installations depends on the rack’s forced cooling arrangement.

The module supplies the SIMATIC S5 CPU and the internal control circuits of the rack modules. Trace the field supply for the digital inputs and digital outputs separately on the cabinet drawing. Check which rail is affected first. Loss of the rack’s 5 V supply and loss of 24 V to sensors and actuators produce different symptoms.

24 V input and 5 V output

The S5-115F data table for the 7ND31 specifies a 19.2–30 V DC input range, 5.4 A rated input current at 24 V and 132 A maximum inrush. The specified fanless 5 V load range is 0.3–7 A. The module has electronic short-circuit protection and an internal primary fuse.

When tracing the S5 connections, identify L+ and M for the 24 V input and check the PE connection against the cabinet’s protective earthing diagram. Voltage can still be present at the input terminals with INT DC POWER switched off. Isolate the cabinet supply before working on the terminals or rack connections.

Rack, cooling and hardware version

The CR 700-1 central rack, ER 701-2 expansion rack and S5-115H expansion rack are different assemblies. Record the full rack order number and the total 5 V load when selecting a spare. If only the expansion rack is affected, check its supply and the connection between the interface modules separately.

For an S5-115U with an IP 244 temperature controller such as the 6ES5 244-3AA21, Siemens specifies 7ND31 hardware version 2 or later and a battery-backed slot for the IP 244. This requirement applies to the IP 244 installation.

Identifying the 7ND31, 7ND32 and 7ND41

Siemens lists the 6ES5 951-7ND41 as the successor to the 7ND31 in the S5-115F table. The 7ND21 appears in the same table with different isolation and voltage-monitoring requirements. The 7ND32 and 7ND51 are separate order numbers. Record the supply code, rack, cooling arrangement and monitoring requirements together when replacing a unit.

Front panel and battery backup

During PLC fault finding, record the 5 V DC indication and then the BATT LOW status. EXT BATT is the external backup connection. Before removing power, verify the STEP 5 project backup and identify what is held in CPU RAM and what is stored on the S5 memory card.

Editor’s note

Before ordering a spare, record the 951-7ND31 nameplate, hardware version and rack order number together. Ask for photos of the front terminals and rear connection.

If the 5 V rail drops at startup, have qualified maintenance staff check the 24 V input during switch-on. A cabinet supply that reads correctly at idle can sag during inrush.

Read the 7/15 A marking in the context of the installed rack. On an S5-115F, use 7 A as the limit for the total 5 V load.

If BATT LOW is lit, confirm the program backup and any required RAM data before shutting down. For a used unit, check whether a battery is included.

Ask for a test record showing the 5 V reading under load, the front-panel indications and the rack order number used for the test.

OtomasyonAVM resources and PDFs

+ SIMATIC S5-115U system and CPU pages · CR 700-1 central rack

+ OtomasyonAVM S5 PDF and manual archive

Related topics

+ 6ES5 951-7ND21 · 6ES5 951-7ND32 · 6ES5 951-7ND41 · 6ES5 951-7ND51

Browse Siemens S5

+ SIMATIC S5 power supplies · SIMATIC S5 · Used Siemens automation equipment

Selling this power supply? Send a nameplate photo, quantity, operating condition and asking price to otomasyonavm@gmail.com.

External references

+ Siemens S5-115F Manual, Volume 1 · Page 8-7 gives the exact-model ratings. Page 3-32 covers the current limit and successor.

+ Siemens S5-115U Manual, 6ES5 998-0UF33 (French) · Section 3.4.1 covers isolation and forced cooling.

+ Siemens IP 244 / FB 162 Manual · Section 2.3 covers hardware version and slot requirements.

+ Adegis 6ES5 951-7ND31 parts listing · Exact order number listing for S5-115U/H.