6ES5 700-1LA12
Siemens 6ES5 700-1LA12 CR 700-1 central rack
The 6ES5 700-1LA12 is the CR 700-1 rack for a CC 1 central controller in a SIMATIC S5-115U system. This SIMATIC S5 mounting rack connects the power supply, CPU and I/O cards through the backplane. It measures 483 × 303 × 47 mm (W × H × D) and weighs 5 kg.
Slot layout and module selection
The PS slot takes a PS 951 power supply, and the CPU slot takes the S5-115U processor. Siemens lists the CPU 941–945 range. The CPU 944 and CPU 945 are two examples. The rack has seven I/O slots numbered 0–6 and a dedicated IM slot.
Check the full part number against Figure 3-4 when selecting digital inputs, digital outputs, combined I/O or analogue modules. Analogue modules in slots 4, 5 and 6 require an IM 306. The compact 6ES5 466-3LA11 analogue input module uses slot 0.
Centralised expansion
The IM slot takes an IM 305 or IM 306. The IM 305 connects one expansion unit. An IM 306 supports up to three expansion units in a centralised layout. The ER 701-0 and ER 701-1 are expansion racks for this arrangement. If the IM slot has no interface module, Siemens specifies that the terminating connector stays in place.
Siemens gives card-specific slot and adapter requirements for certain communications processors and positioning modules. Figure 3-4, for example, shows the CP 530-7 in slot 0. For distributed expansion, check the separate interface layouts of the CR 700-2 and CR 700-3.
- Check the 700-1LA12 label before buying a spare. Confirm separately whether the offer includes the PS 951, CPU, IM and terminating connector.
- Back up the STEP 5 program before removal. Photograph the module order in slots 0–6, the front connectors and the analogue range settings.
- After safely isolating power, inspect the backplane pins and card guides. Check the PS, CPU and IM sockets for heat damage, loose connections or bent pins.
- If analogue data is missing from slots 4–6, check the IM 306 and STEP 5 address before replacing a module. If a 466-3LA11 is installed, confirm that it is in slot 0.
- If the central I/O works but the expansion I/O is missing, check the IM and the link cable first. On a rack without expansion, check the terminating connector in the otherwise empty IM slot.
- After replacement, keep actuator power circuits isolated while you monitor inputs one at a time in STEP 5. Compare analogue readings with the addresses and signal ranges you recorded before removal.
To offer a rack for sale, send photos of its label and backplane to otomasyonavm@gmail.com.
PDFs and Siemens references
S5-115U manual, Figure 3-4 (EN) · Technical data, p. 15-6 (EN) · Siemens ST 50 catalogue, p. 3/60 (EN).
Related topics
About Siemens S5 PLCs · IM 306 interface · ER 701-1 expansion rack
Used Siemens · S5 racks · CPU 90U–115U · Siemens S5 · Used Siemens main page