6ES5 951-7ND41
Siemens SIMATIC S5 6ES5 951-7ND41 PS 951 Power Supply
The Siemens 6ES5 951-7ND41 is a PS 951 rack power supply listed for the S5-115U, S5-115H and S5-115F in the SIMATIC S5 family. It takes 24 V DC and supplies 5 V DC to the rack electronics. In S5-115U and S5-115H systems, the rated output is 7 A without a fan and 15 A with the appropriate fan assembly. In an S5-115F system, Siemens specifies fanless operation with a 7 A maximum.
The PS 951 supplies the CPU and I/O control electronics in the S5-115U rack. Include the current drawn by the CPU 943, CPU 944 or other installed S5 modules when calculating the rack load. Refer to the cabinet drawings for the separate load circuits that feed field sensors and actuators.
Input, rack output and auxiliary supplies
Siemens specifies an operating range of 19.2–30 V DC at the L+ and M input terminals. The rated input current at 24 V DC is 5.6 A, and the 5 V rack output has a ±1.5% voltage tolerance. The S5 power supply range also includes 24 V DC units such as the 3 A 7NB21. Check the 5 V current rating when matching a spare.
The PG/OP output is rated at 5.2 V DC and up to 2.5 A. The 24 V auxiliary output is rated at up to 0.35 A. Keep these outputs separate in your load calculations and check each one against its own rating.
When does the 15 A rating apply?
On the S5-115U, Siemens calls for a fan assembly when the 5 V load exceeds 7 A or when high-power modules are fitted. Match the fan input to the available supply. The 24 V DC fan assembly and the 115/230 V AC fan assembly require different feeds. Use the full rack number, such as 6ES5 700-1LA12 or 6ES5 700-2LA12, to check mounting dimensions and airflow.
7ND41, 7ND51 and other PS 951 variants
Table 3-7 of the S5-115H manual lists the 7ND41 as isolated and the 7ND51 as non-isolated. The S5-115F manual lists the 7ND41 as the replacement for the 7ND31. It also calls for higher-level external voltage monitoring with the 7ND21. Check other variants, such as the 7ND32, by their own order numbers.
When comparing DC-input PS 951 units such as the 7ND12, check the current rating, cooling and rack configuration together. The 7LD21 and 7LD12 are AC-input variants. Match the replacement to the cabinet supply and the rack wiring.
Battery backup and front panel
Siemens lists the 7ND41 as supplied without backup batteries. The unit has two battery holders. Use the BATT LOW indicator to identify a backup battery issue. Before replacing the supply, record the installed CPU order number, such as CPU 943-7UB11 or CPU 944-7UB11, and check its memory backup procedure.
Editor’s note
Photograph the 7ND41 suffix and identify the rack as 115U, 115H or 115F. On an S5-115F job, record the 7 A system limit on the work order.
If an S5-115U or S5-115H rack draws more than 7 A, check the fan type, its supply and the airflow path. Use the 15 A rating only after confirming that the required cooling is working.
If power drops at startup, have qualified maintenance staff check L+ to M under load first. Record the 24 V input and the 5 V rack output separately.
If BATT LOW is on, verify the STEP 5 project backup and the memory retention procedure before removal. Record the condition of both battery holders and any external backup connection.
When buying used, ask for a clear label photo, a 5 V reading under load and the cooling setup used during the test. If you have a unit to sell, email a label photo, quantity, known condition and asking price to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
+ SIMATIC S5-115U CPUs and racks
+ SIMATIC S5 manuals and PDF archive
+ Siemens S5-115H system manual · 7ND41 specifications, p. 17-10 (EN)
Related topics
+ 6ES5 951-7ND31 PS 951 power supply
+ 6ES5 951-7ND51 PS 951 power supply
+ 6ES5 981-0HA21, 24 V DC fan assembly
Browse SIMATIC S5
+ Used Siemens automation equipment
External references
+ Siemens S5-115U system manual · 7ND41 specifications, p. 15-13 (EN)
+ Siemens S5-115F system manual · power supply selection, Table 3-3 (EN)