6ES5 244-3AA21
Siemens 6ES5 244-3AA21 is the IP 244 temperature control module for temperature zones in SIMATIC S5-115U, S5-135U and S5-155U systems. It compares the analog temperature reading with the setpoint and calculates the heating or cooling demand. Self-tuning helps establish PID settings for the zone.
Measurement and control. The exact-part listing identifies thermocouple, RTD and millivolt inputs. The IP 244 family signals control demand through pulse-duration digital outputs. Use the machine wiring diagram to verify the 3AA21 channel count and pinout.
PLC interface. Siemens pairs 3AA21 with FB 162 with 32 messages and FB 162 with 64 messages, version I. The block transfers parameters and status data between the CPU and the module. The module requires a battery-backed slot.
OtomasyonAVM PDF archive
+ Shared Siemens S5 PDF archive
What to check on the machine
Sensor circuit. Thermocouples and Pt100 sensors use different wiring. Compare the sensors and match the thermocouple type to the machine drawing and channel settings. See S5 analog modules and S5 cables and connectors when tracing the measurement circuit.
Heater control. Trace the PID output demand and heater power circuit separately. If the cabinet uses S5 digital output modules or solid-state relays, confirm which temperature zone each one serves.
Module replacement. Record the FB 162 version in the SIMATIC S5 project. The 6ES5 244-3AA13 is a separate order number in the same family of S5 special modules and function modules. Check the full order number and FB 162 version together when selecting a spare.
Installation and power supply. Check the battery backup at the S5 rack slot. The Siemens manual gives these minimum hardware revisions for S5-115U power supplies. Use 951-7LB14 from version 6, 951-7LD12 from 2, 951-7NB13 from 3, 951-7ND12 from 4, 951-7ND21 from 3 and 951-7ND31 from 2. Check the 6ES5 491-0LA11 adapter casing against the S5-115U rack layout.
Editor’s note
Photograph the module label, slot number and front plugs before removal. Check the 3AA21 suffix and hardware revision on the replacement label.
Back up the STEP 5 project, the FB 162 version and the temperature zone parameters. After replacement, verify the mapping one zone at a time.
If the reading jumps in a single zone, check the sensor type, thermocouple polarity and terminal connections before replacing the module. Compare the reading with an independent temperature reference.
If several zones drift together, check the common measurement wiring and thermocouple cold-junction compensation against the machine drawings. If the fault appeared after a power outage, check the backup circuit as well.
If the reading is correct but the zone stays cold, check the module’s heat demand and the field SSR or contactor circuit separately. Keep heater power safely isolated during the initial function test.
Before starting auto-tuning, verify the sensor belongs to the correct zone and the overtemperature protection works. When buying a used module, ask for a measurement and control test as well as a power-up photo.
Have this module to sell? Send the label photo, quantity, working condition or fault details, and asking price to otomasyonavm@gmail.com.
Related topics
+ 6ES5 244-3AA13 IP 244 temperature control module
Navigation
External references
+ Siemens IP 244 / FB 162 manual (PDF) · p. 1-4, 3AA21 and FB 162 compatibility diagram.
+ Siemens installation section (PDF) · p. 2-14, battery-backed slot and S5-115U power supplies.
+ PLC Hardware 6ES5 244-3AA21 part listing · thermocouple, RTD and mV.
+ Radwell 6ES5 244-3AA21 part listing · IP 244 and thermocouple.