6ES5 244-3AA13

Siemens 6ES5 244-3AA13 · IP 244 temperature control module

The 6ES5 244-3AA13 is an IP 244 temperature control module with 13 thermocouple measurement channels for SIMATIC S5. It measures machine heating zones and uses pulsed 24 V DC digital outputs to control heating or heating and cooling. The control algorithm runs on the module. Setpoints and parameters are exchanged with the PLC using the 32-message FB 162.

+ OtomasyonAVM Siemens SIMATIC S5 PDF archive

Inputs and sensor selection

X3 has 16 analog inputs. The factory setting assigns channels 0–12 to 0–51.2 mV thermocouple signals. Siemens lists DIN 43710 types L, K and S. When selecting a type K or another thermocouple, match the sensor type to the PLC parameter. For legacy type L sensors, check the thermocouple standard and sensor label.

Channels 13 and 14 are set at the factory to monitor 0–20.48 V transmitter signals against limits. Channel 15 uses a three-wire Pt100 to measure terminal temperature for cold-junction compensation. The Pt100 and thermocouples serve different roles in this wiring arrangement.

Control outputs and power supplies

This special function module for SIMATIC S5 supports parameter selection of P, PI, PD and PID control. Record the P, I and D settings by zone. In PID temperature control, two-position operation controls heating and three-position operation assigns separate outputs to heating and cooling. The PLC control program exchanges setpoints and parameters with the card.

X4 provides 17 control outputs and the K comparator output, which monitors channel 13. X4 also carries the heating enable input. The digital outputs are rated 24 V DC, 120 mA. The module electronics use 5 V DC from the rack. The outputs use 24 V DC from the front-panel L+ terminal. When testing the power supply and load circuit, check the SSR or relay control input. When comparing solid state relays, match the input voltage and current to the module output rating.

Rack, addressing and module replacement

Siemens lists S5-115U, S5-135U, S5-150U and S5-210A systems. The rack must provide a battery-backed slot. For the S5-115U, check the 6ES5 491-0LA11 adapter casing and the power supply hardware revision.

The module occupies 32 consecutive addresses in the S5 system. A start address of 64 occupies addresses 64–95. The 3AA13 and 3AA21 use different FB 162 versions. Siemens pairs the 3AA13 with the 32-message block and the 3AA21 with the 64-message version I.

Editor's note

+ When buying used, ask for photos showing the full 3AA13 label and the X3 and X4 connectors. Ask the seller to demonstrate a thermocouple reading and a switching control output in the same test.

+ Back up the STEP 5 project and temperature parameter blocks before removal. After safely isolating power, photograph J76/J77, the jumpers, the rack and the slot number.

+ If one zone reads incorrectly, check its thermocouple type, polarity and extension cable. If several zones drift together, inspect the three-wire Pt100 on channel 15 and its thermal contact with the thermocouple terminals.

+ If temperatures are displayed but the zones stay cold, check L+ load power and the heating enable input against the machine drawings. If the red short-circuit LED is on, isolate power before checking the affected X4 circuit and its load separately.

+ If the spare card receives no PLC data, compare the start address, 32-address range and FB 162 version with the old installation. Then check that the expected setpoint is written to the correct zone.

+ With heater power isolated, check a zone's sensor reading and corresponding output command. Record the zone-to-output mapping and follow the machine commissioning procedure for the first heat-up.

Related topics

+ 6ES5 244-3AA21 IP 244 temperature control module

+ 6ES5 491-0LA11 S5-115U adapter casing

+ Using PID for temperature control

Used Siemens equipment

+ S5 special function modules

+ Siemens SIMATIC S5 models

+ Used Siemens equipment overview

To sell a used card, email the full order number, quantity, condition, label and connector photos, and asking price to otomasyonavm@gmail.com.

External sources

+ Siemens 3AA13 operating instructions B8576351-02, specifications and wiring (EN)

+ Siemens IP 244 manual, FB 162 matching on p. 1-4 and slot requirements on p. 2-14 (EN)

+ Siemens 6ES5 244-3AA13 data sheet (EN)