6ES5 951-7LB14

The Siemens 6ES5 951-7LB14 is a PS 951 power supply for the SIMATIC S5-115 range. It takes a 115/230 V AC input and provides 5 V DC at 3 A to the rack. The order number is listed without a backup battery. The S5-115U manual identifies this version as a supply that does not generate the DSI signal, which limits the positioning and communications modules it can support.

In a SIMATIC S5 installation, the 5 V rail powers the CPU and the internal circuits of the installed modules. When selecting a spare for a rack such as the CR 700-3 central rack, check the rack designation and the order numbers of the cards fitted to it.

115/230 V AC input and 3 A rack output

115/230 V AC is the input specification. The 3 A rating applies to the 5 V DC rack output. Before installation, check the unit’s nameplate and voltage selector position against the cabinet supply.

When adding a card to an S5 rack, include the CPU and the existing modules in the 5 V load calculation. If only a group of digital inputs or digital outputs is affected, trace that group’s field power supply separately in the cabinet drawings.

Which cards require DSI?

Siemens excludes the 7LB14 and 7NB13 from use with the IP 246 and IP 247 positioning modules because those cards require DSI. The restriction also applies to the CP 513, 526, 527, 535, 580, 581 and 143 communications processors. The CP 524 and CP 525 are excluded from 3 A supplies on current consumption grounds.

Comparing the 7LB14 with other PS 951 versions

The 6ES5 951-7LB13 is also listed as a 115/230 V AC, 3 A version. The 6ES5 951-7NB13 takes a 24 V DC input and supplies 3 A. The 6ES5 951-7LD12 is in the 7/15 A class. Check the input type, 5 V load and module signal requirements together when choosing a replacement.

Commercial catalogues list the 7LB14 for the S5-115U/H. The 3 A AC power supply specification in the Siemens S5-115H manual hosted by OtomasyonAVM covers the 6ES5 951-7LB21. For an S5-115H replacement, confirm the exact order number against the documentation for the installed rack.

Editor’s note

Record the nameplate and selector position. Take a service photo that captures both the full 7LB14 code and the input markings. Catalogue descriptions differ on AC and DC, so the installed unit’s markings are particularly useful.

Inventory the cards actually fitted. Read the IP and CP labels on the rack. Cabinet records can lag behind hardware changes made during earlier repairs.

Check how the CPU retains its program. Before isolating power, confirm that the program backup is current and establish how the RAM is backed up. Record the order number of any fitted S5 memory card.

Record how much of the system went down. If the CPU stopped as well, check the rack supply alongside any voltage drop at the cabinet input. If the fault stays in one expansion unit, review that unit’s supply and connection records.

Ask how the spare was tested. When buying a used PLC power supply, ask which input setting was used and what load was applied when the 5 V output was measured.

OtomasyonAVM references and PDF archive

Browse our Siemens S5 PLC section for series and model pages and our OtomasyonAVM S5 PDF page for published manuals. The S5-115H system manual (English PDF) covers 115H racks and the power supply variants documented for that system.

Related topics

Use the S5 positioning module index to identify IP cards and the S5 CPU 90U–115U index to compare processor and central-unit order numbers.