Delta DVP14SS11T2 DVP-SS PLC – 8 Inputs, 6 NPN Outputs
The Delta DVP14SS11T2 is a compact DVP-SS PLC CPU powered by 24 V DC, with 8 digital inputs and 6 NPN transistor outputs. It suits conveyors, part counting and sequential machine automation. The DVP-14SS Turkish technical sheet specifies a capacity of 3,792 program steps.
Power supply and terminal groups
The CPU takes 20.4–28.8 V DC. Inputs X0–X7 use 24 V DC signals. When connecting a PNP or NPN inductive sensor, wire the S/S input common according to Delta’s sink/source diagram. The output groups are C0 → Y0, C1 → Y1 and C2 → Y2–Y5. An NPN output sinks load current to 0 V.
The transistor output table gives a 30 V DC voltage limit and 0.3 A per point at 40 °C. At 55 °C the specified value is 0.1 A per point. Select the load for the temperature inside the control panel. For a relay or solenoid coil, verify the coil current and suppression device. Keep signal wiring apart from power cables and follow the grounding diagram.
Counting and machine applications
For part counting, use the high-speed counter to capture short sensor pulses. The DVP-14SS technical sheet lists 10 kHz for one-phase counting and 7 kHz for two-phase counting. With an encoder, match the output type, voltage and A/B inputs to the chosen counter mode. For pulse-based position control, check which Y address the selected instruction uses in the SS documentation.
On a sorting line, count items from a sensor, drive the diverter at the target count and reset the counter after confirmation. An HMI can show the count and stop reason separately. Where production logging is needed, send both to SCADA. For more digital points or analog signals, select compatible DVP expansion modules for the CPU.
WPLSoft, programming cable and RS‑485
Delta lists WPLSoft for PLC programming on this model. Open the project with the DVP-SS CPU family. The documented PC cable to COM1 RS‑232 is DVPACAB215 (1.5 m). A PC with USB can use a suitable USB-to-RS‑232 adapter. If working with an existing ISPSoft installation, check for the DVP-SS CPU profile first.
COM2 is the RS‑485 serial port. For industrial communications, match the station address, baud rate and parity when adding a panel or drive to an RS‑485 line. If the project uses Modbus RTU, confirm the protocol in the existing CPU software and project settings.
Related models
The DVP14SS11R2 is the corresponding relay model. The DVP14SS11T and DVP14SS11R are other members of the SS family. The DVP14SS211T belongs to the DVP-SS2 family. Check the terminal layout and project compatibility before replacing a CPU. For a new panel design, see the Derell B Series PLCs.
Editor’s Note
For a used unit, check the full DVP14SS11T2 label. Pay attention to the 11T2 and 211T suffixes.
Ask for photos of the power connector, COM1 socket and C0/C1/C2 terminals.
If you can read the existing program, save a backup before making changes.
Test inputs with a known 24 V signal and test each output group separately with a suitable DC load.
If the panel uses RS‑485, record its address, baud rate and parity before replacement. Verify the panel readout on the bench.
PDFs and technical documents
Related document index Delta DVP PLC files. The DVP-SS instruction sheet includes power wiring, sink/source wiring and the transistor output diagram. The Turkish technical sheet lists WPLSoft, the programming cable, memory and device specifications.
DVP14SS11T2 main page · DVP PLC series · Delta PLC accessories · Delta external terminals · Delta PLC · Used Delta models · Delta PLC and HMI manuals
Delta AS PLC · Delta AH PLC · Delta TP panels and remote I/O
External references
Delta DVP-SS Instruction Sheet (2009) · Delta DVP-14SS PLC Kısa Bilgi Dokümanı (TR) · Delta DVP-PLC Application Manual (2022, model index)