Delta DVP14SS11R2

Delta DVP14SS11R2 – DVP-SS PLC with 8 Inputs and 6 Relay Outputs

Delta DVP14SS11R2 is a compact CPU in the original Delta DVP-SS family, with 8 digital inputs and 6 relay outputs. Its built-in EEPROM holds 3,792 program steps. The R2 suffix identifies this relay model in the original SS family. The DVP14SS211R belongs to the later DVP-SS2 family. Compare the program and terminal layout for the exact model before replacing a unit.

Power supply, inputs and relay commons

The CPU requires 24 V DC (20.4–28.8 V DC). A suitable Delta DVPPS01 or DVPPS02 can power the panel circuit. X0–X7 are 24 V DC inputs with a shared S/S terminal. For three-wire PNP and NPN sensors, connect S/S to 0 V for PNP or +24 V for NPN.

The six relay outputs are addressed Y0–Y5. Y0 uses C0, Y1 uses C1 and Y2–Y5 share C2. Delta lists 1.5 A per output, 5 A per common and voltage limits of below 250 V AC or 30 V DC. Check the contact load against the load type and inrush current. Control a motor through a suitable contactor. Use the relay contacts for ordinary switching duties.

Programming software, cables and communications

Select SS or the ES/EX/SS group, depending on the software version, in WPLSoft to read, edit and monitor the ladder program. Delta’s legacy ISPSoft manual specifies CPU firmware V6.2 or later for DVP-SS/ES/EX. Check the unit’s firmware and whether your ISPSoft version offers the appropriate CPU type before connecting.

Connect the PC through the CPU’s 8-pin mini-DIN RS-232 programming port. Delta lists the DVPACAB215 (1.5 m), DVPACAB230 (3 m) and DVPACAB2A30 (3 m) for this series. On a PC without a serial port, install the driver for the RS-232 adapter and select its COM port in the software. A separate RS-485 port handles communication with field devices. Check the serial settings and protocol used in the existing project.

Expansion and applications

Delta’s DVP-SS manual specifies up to 128 I/O points, depending on the configuration. The DVP08SM11N adds inputs, the DVP08SN11R adds relay outputs, and the DVP08SP11R adds mixed I/O. For process measurements, check CPU and module documentation for compatible analog modules and temperature modules. The PLC programming guide covers sensor inputs, sequence control and communication.

Editor’s Note

Read the full DVP14SS11R2 model number when buying used. Check the program and terminal layout before transferring wiring to another CPU.

Upload the program from the PLC to the PC and save a backup. Check the RUN/STOP switch and inspect the RS-232 socket for bent pins.

With the output LED illuminated, verify that each relay contact conducts with a suitable low-voltage test load.

If Y0 and Y1 work and Y2–Y5 fail together, check the C2 common first. If the terminal connection is sound, test each relay contact separately.

If inputs flicker when a contactor energises, check cable routing, cabinet grounding and sources of electromagnetic interference.