Delta DVP14SS11R
Delta DVP14SS11R – DVP-SS PLC with 8 inputs and 6 relay outputs
The Delta DVP14SS11R is a compact PLC CPU in the Delta DVP-SS series with eight digital inputs and six relay outputs. The nominal supply is 24 V DC, with a range of 20.4–28.8 V DC. Delta’s legacy ES/EX/SS specifications list a 3,792-step EEPROM program capacity. The CPU can read sensors and push buttons and control auxiliary relays or contactors.
X0–X7 inputs and C0/C1/C2 relay commons
X0–X7 are 24 V DC sink/source digital inputs. All eight share the S/S common. Check the PNP/NPN sensor type and the cabinet’s S/S wiring together.
Y0 uses C0, Y1 uses C1, and Y2–Y5 share C2. Delta specifies 1.5 A per output and 5 A per common for resistive loads on the relay contacts. Refer to the manual for inductive load ratings and contact protection. For high-speed pulses, check the transistor-output DVP14SS11T and its pulse limits.
WPLSoft, serial programming cable and RS-485
Use WPLSoft to read, back up and monitor the existing ladder program. Verify the DVP-SS project target and CPU version. For ISPSoft, check that the installed release supports this legacy CPU target. Use COMMGR to select the RS-232 driver and the correct COM port.
Connect to COM1, the 8-pin Mini-DIN RS-232 programming port. Delta’s legacy SS documentation lists the DVPACAB215, DVPACAB2A30 and DVPACAB230 PC cables. On a USB-equipped computer, use the serial cable with a suitable USB-to-RS-232 adapter and its driver. The connector on the PLC is a serial Mini-DIN port.
COM2 provides RS-485 communication with field devices. For an existing HMI or drive connection, copy the station address, baud rate, parity and protocol from the original project.
Expansion and related models
Add digital points with compatible right-side DVP-S expansion modules. Delta’s legacy SS manual lists the DVP16SP11R digital expansion unit and the DVP04AD-S analog input module. Select a separate analog I/O module for signals such as 4–20 mA and 0–10 V. The DVP14SS11R2 and DVP14SS11T2 belong to the DVP-SS family. The DVP14SS211R belongs to the DVP-SS2 family. Compare terminal commons, the program target and the module order before replacing the CPU.
Editor's Note
When buying used, inspect the full DVP14SS11R label, the C0/C1/C2 markings and the side expansion connector.
On the bench, check the 24 V DC supply with a multimeter first. If the ERROR LED flashes rapidly, measure the voltage at the CPU terminals.
Read and back up the current project. Record the serial settings and any expansion module order before downloading a test program.
Test the relay outputs individually with a suitable low-voltage test load. If Y0 and Y1 work and Y2–Y5 stay off, check the C2 common first.
If inputs become erratic when a contactor switches, check sensor cable routing, electromagnetic interference and grounding.