Delta DVP14SS11T
Delta DVP14SS11T — DVP-SS PLC with 8 inputs and 6 NPN outputs
The Delta DVP14SS11T is a 24 V DC PLC CPU from the original DVP-SS series. It has 8 digital inputs (X0–X7) and 6 NPN transistor outputs (Y0–Y5). Delta’s application manual specifies 3,792 program steps for the original SS series. Compatible DVP expansion modules can add I/O points.
On a conveyor, a photoelectric sensor can detect products and a limit switch can report travel limits. The PLC reads those inputs and can operate an appropriately rated interface relay or DC indicator. Check both the PLC I/O type and the electrical requirements of the load.
S/S input common and NPN output groups
Connect the shared S/S input common to +24 V DC for NPN sensors or 0 V for PNP sensors. The NPN and PNP and sink/source guides show current direction.
The DVP-SS wiring diagram shows output groups Y0/C0, Y1/C1 and Y2–Y5/C2. For NPN wiring, connect the relevant C terminal to the load supply 0 V and wire the load between supply positive and its Y output. When the output turns on, it sinks current to 0 V. The SS wiring sheet specifies 0.3 A per channel at 40 °C for transistor outputs. For a coil load, check coil current and the manufacturer’s flyback diode guidance.
High-speed pulses, programming and communication
Delta’s SS programming manual gives a PLSY command range of up to 10 kHz on Y0 and Y1. Match the DC pulse input, common and current limits of a stepper motor drive to the PLC’s NPN output. For encoder feedback, choose the inputs for the required high-speed counter mode.
Use WPLSoft or an ISPSoft version supporting the original SS for PLC programming. Select the DVP-SS CPU family. The front programming port is an 8-pin mini-DIN COM1 RS-232 connection. Delta’s application manual shows the DVPACAB2A30 serial cable for this COM1 interface. A compatible USB-to-RS-232 adapter can connect it to a USB-equipped PC. See Delta programming cables for other options. With ISPSoft, select the correct COM port in COMMGR.
COM2 RS-485 supports field communication with suitable serial settings. Match the station address, speed and communication format. RS-232 and RS-485 use different electrical interfaces. For a project using Modbus RTU, check that the CPU firmware and serial settings support that mode.
Editor’s Note
Read the complete nameplate on a used unit. DVP14SS11T identifies the original SS and DVP14SS211T identifies the second-generation SS2. Delta specifies 8K steps for the SS2 family. Check the CPU selection and program size before migrating a project.
Back up the program and any required retained D values. Check COM1 communication and RUN/STOP operation first on the bench.
If an output LED is on and the load stays idle, check its C terminal’s 0 V return. A fault on C2 can affect the entire Y2–Y5 group.
Test Y0 and Y1 individually at low frequency. Safely prevent mechanical movement before checking the drive’s pulse input.
Check supply and commons with a multimeter. When a sensor changes state, confirm that its input LED and the X address in the software change together.