Delta DVPEN01-SL
Delta DVPEN01-SL is an Ethernet communication module that mounts on the left side of a compatible DVP PLC CPU. Its 10/100 Mbit/s RJ‑45 connection exchanges data over Modbus TCP. In industrial communication applications it enables HMI and SCADA systems to access PLC data.
CPU compatibility and connection
Delta’s product page lists the DVP-EH3-L, DVP-MC, DVP-SA2, DVP-SE, DVP-SV2 and DVP-SX2 families. The 2026 module manual also lists DVP-SV3 and DVP-SX3 support with module firmware V2.18 or later. SMTP, SNMP and Mitsubishi MC protocol are unavailable with SV3/SX3. Check the complete CPU code, left expansion interface and module firmware together.
The module draws 24 V DC from the CPU’s internal bus. It consumes 1.5 W and weighs approximately 92 g. Its RJ‑45 port automatically detects a 10 or 100 Mbit/s link. Auto MDI/MDIX allows a standard straight-through Cat5e Ethernet cable. Start with a short cable for bench testing. Use an Ethernet switch for multiple devices and allow cable clearance inside the control panel.
IP addressing and Modbus TCP
The documented factory IP address is 192.168.1.5, subnet mask 255.255.255.0 and gateway 192.168.1.1. A used unit may retain changed settings. On a bench network with the default module address, choose a free PC address on the same subnet, such as 192.168.1.10/24. When several modules are present, identify the unit by its MAC address. The LINK LED shows the physical Ethernet connection. Verify that you can read data separately.
In Modbus TCP, a panel or PC can act as the client and the DVPEN01-SL as the server. The module can also act as a client and exchange data with other devices. Check the IP address, PLC register area and address base in the HMI driver. Modbus TCP and EtherNet/IP are distinct protocols. Select the Ethernet protocol that matches the driver. When migrating from Modbus over RS‑485, enter the Ethernet connection settings and verify the Modbus addressing instead of reusing the RTU serial settings.
DCISoft, PLC software and cables
Use DCISoft to set up networking and data exchange. Connect over Ethernet using Auto-Search or the known IP address. The module’s RS‑232 communication port is for parameter settings only. Delta lists the UC-MS030-01A, UC-MS010-02A and UC-PRG020-12A cables for this service connection. If the PC has no serial port, verify the USB–RS‑232 adapter and COM number.
Delta’s manual shows Ethernet access to a compatible PLC through WPLSoft. For an ISPSoft project, choose the connection supported by the host CPU and check COMMGR. On SV3/SX3, DCISoft can open from the DIADesigner hardware view. The CPU runs the automation program. For RTU-EN01 mapping described in the 2026 manual, the module requires firmware V2.20 or later.
Related communication modules
In the DVP Slim communication range, DVPDT01-S and DVPDNET-SL are DeviceNet options, DVPPF01-S and DVPPF02-SL cover PROFIBUS, and DVPCOPM-SL covers CANopen. See DVPSCM12-SL for serial communication or DVPSCM52-SL for BACnet MS/TP. Compare the host family, expansion side and protocol before replacement.
Editor’s Note
Start with the CPU’s left interface and the complete module label. A clean RJ‑45 socket tells you little about the condition of the side bus connector.
Start on a separate bench network. If LINK is off, try a known-good cable and switch port. If LINK is on but no data arrives, check the IP address, selected protocol and register address.
On a used unit, back up the existing settings in DCISoft before making changes. Confirm communication by reading a known PLC register first.
Ask for photos of the label, RJ‑45 socket and side connector before buying. A successful read with a compatible CPU tells you more than the POWER LED alone.
If the application needs e-mail alarms, check the mail server requirements. Delta’s manual states that this module lacks TLS/SSL support.
PDF manuals and technical documents
See the Delta DVP PLC files page and section 13.1 of the DVP Series Module Manual. In the 6 January 2026 edition, specifications are on PDF pages 339–340, DCISoft setup starts on page 349, and default network settings are on page 359. The 2009 model manual is an additional reference for older hardware and software screens.
DVPEN01-SL main page · DVP expansion modules · DVP PLC series · Delta PLC · Used Delta models · Delta manuals
External references
Delta DVP Series Module Manual (2026) · Delta DVPEN01-SL Operation Manual (2009)