Delta DVPSCM52-SL

Delta DVPSCM52-SL – BACnet MS/TP and Serial Communication Module

Delta DVPSCM52-SL is a communication module that mounts on the left expansion bus of a compatible DVP PLC. Its two RS-485/RS-422 ports support BACnet MS/TP slave, Modbus ASCII/RTU and user-defined UD Link. On the BACnet network, a supervisory controller can read or write mapped PLC values. In building automation, these can include pump status, HVAC readings and alarms sent to a SCADA or building management system.

Ports, power and field wiring

COM1 and COM2 are configured separately. The CPU’s internal bus supplies 24 V DC and the module consumes 1.5 W. Each port has switchable 120 Ω termination. In Delta’s terminal table, RS-485 uses 3 = D+, 4 = D−, 5 = SG. In RS-422 mode, 1/2 = TX+/TX− and 3/4 = RX+/RX−. Check the other device’s labels against its own terminal diagram.

In industrial communication, the port type, protocol and line speed are separate settings. Modbus ASCII, Modbus RTU and BACnet MS/TP are separate protocols. General serial port settings span 1200–460800 bit/s. Use the BACnet rates listed below for MS/TP. Check termination at the physical ends of the RS-485 bus. When laying out panel components, route the serial pair away from motor cables. Follow the manufacturer’s shielding and grounding diagrams to reduce electromagnetic interference.

SCMSoft, CPU compatibility and programming cables

Configure module ports and objects in SCMSoft. Delta’s manual specifies DCISoft V1.08 or later for BACnet setup. The manual lists DVP-SA2, DVP-SX2 and DVP-SE among compatible CPU families. DVP-SV3/SX3 support requires module firmware V1.10 or later. Check the CPU model and firmware before fitting the module on the left expansion side.

Program the supported CPU in WPLSoft or ISPSoft. Set up ISPSoft communication through COMMGR. For example, the SA2 COM1 RS-232 communication port uses UC-PRG020-12A from PC USB or UC-MS020-01A from PC RS-232. Choose the programming cable for the CPU port. On SV3/SX3, use DIADesigner for the CPU project. SCMSoft can be opened from the module icon in the hardware configuration.

BACnet MS/TP settings and AV/BV mapping

In SCMSoft, set the selected port’s protocol, physical interface and MAC address. Use a unique MAC address on the MS/TP segment within the supervisory controller’s supported range. Delta’s BACnet setup section lists 9600, 19200, 38400 and 76800 bit/s. Match the speed to the supervisory controller. This module joins a BACnet MS/TP network on its serial port. Use a suitable router where the installation connects to BACnet/IP.

An AV maps a numeric value to two consecutive PLC data registers. A BV maps a binary state to one PLC bit. AV0 at D100–D101 and BV0 at M100 are examples. Verify one status bit and one measurement first when linking the PLC and SCADA. Compare the local HMI display with the supervisory value. According to Delta, with module firmware V1.08 and earlier, the CPU must write an AV/BV before reading it. V1.10 and later support direct reads from the CPU.

Related models and network selection

DVPSCM12-SL is suitable for serial applications requiring Modbus and UD Link. Confirm the 52-SL part number for BACnet MS/TP. DVPEN01-SL is an Ethernet and Modbus TCP option, DVPCOPM-SL serves CANopen applications and DVPPF02-SL serves PROFIBUS DP applications.

Editor’s Note

Check that the label says DVPSCM52-SL. For a used module, ask for photos of the side connector, both serial terminals and the termination switches.

If POWER is off, start with the CPU supply and left expansion connection. Check the module’s RUN status as well.

If TX flashes and RX stays idle, check polarity, the physical port setting, speed and the other device’s address. If the traffic LEDs flash, also verify that the correct object is being read.

If an AV looks wrong, verify the start address of the two registers and the data type at the supervisory controller. For a BV, check that you are monitoring the intended bit.

Before replacing a module, back up the working SCMSoft project, port settings and AV/BV mapping. Test one monitoring point first, then verify the remaining objects in turn.

PDF manuals and technical documents

See Delta DVP PLC files for series documentation. Section 13.5 of the Delta DVP module manual covers terminal assignments, SCMSoft settings, BACnet objects and diagnostic indicators.

Navigation · Delta automation · Delta PLC · DVP PLC series · Expansion modules · DVPSCM52-SL model page

External references

Delta DVPSCM52-SL product information · Delta DVPSCM12/52-SL operation manual (2012)