Delta UC-PRG030-20A is a 3 m programming and communication cable with RJ45 connectors at both ends, used between a computer and the Ethernet port of a suitable Delta PLC or HMI. Delta catalogues list it for PC ↔ PLC/HMI, RJ45 ↔ RJ45 connections. Program transfer, connection establishment and data exchange over Ethernet depend on the connected device's hardware and supported software/protocol.
Although listed under Delta DVP programming cables, this product is not a USB-to-serial converter. It uses the computer's Ethernet network adapter; connecting the cable does not create a new virtual COM port. Devices requiring USB or DB9 connections use different UC-PRG models. Further options appear under DVP communication cables and industrial network cables.
Length, connectors and signal pins
Model: UC-PRG030-20A. Length: 3 m. Ends: RJ45 male ↔ RJ45 male. Purpose: a data connection between suitable Ethernet ports. The cable itself has no IP address, station address or user-downloadable firmware.
Figure 7 in Delta's cable selection guide and the starter kit appendix identify Ethernet signal pins as 1: Tx+, 2: Tx−, 3: Rx+, 6: Rx−. Observe the connector viewing orientation during inspection. An RJ45 housing alone does not establish Ethernet compatibility; CAN, serial or proprietary RJ45 ports require verification against their own wiring diagrams.
Documented Delta device connections
DVP-SE: Delta's cable guide shows UC-PRG030-20A for the built-in Ethernet ports of DVP12SE11R and DVP12SE11T. Mini USB is a separate cable option in the DVP-SE group; having both interfaces on a device does not make their cables interchangeable.
Ethernet modules: Ethernet connection examples are also provided for DVPEN01-SL, DVP-FEN01 and AH10EN-5A. The cable connects to the module's Ethernet port; do not confuse this with the serial port or its settings.
AS and HMI: The AS hardware manual lists UC-PRG030-20A for AS332T-A, AS332P-A and AS324MT-A. For Delta AS PLC series and Ethernet-equipped DOP-B HMI models, verify the required port and software connection using the complete device code. The cable alone cannot add Ethernet capability to an HMI without an Ethernet interface.
IP configuration and programming software
A direct connection requires compatible IP addresses and subnet masks for the computer and device. Two devices on the same network must not share an IP address. Select the correct network adapter and target device address. Connecting the cable does not automatically change the PLC's IP settings or the computer's network configuration.
Select programming software according to the PLC generation. For supported Ethernet connections in ISPSoft, select Ethernet as the communication driver type in COMMGR. Assess WPLSoft support against the particular DVP CPU and software version. DCISoft information may be relevant to network settings on the Delta Ethernet devices it supports. These tools are not drivers installed inside the cable.
Differences from similar UC-PRG codes
UC-PRG015-01A and UC-PRG030-01A are listed for mini USB connections; UC-PRG015-02A and UC-PRG030-02A are listed for USB Type-B. UC-PRG030-10A is a DB9 serial cable, while UC-PRG020-12A belongs to the USB/serial connection options. UC-PRG030-20A is distinguished by its RJ45-to-RJ45 Ethernet connection. Matching cable length or the UC-PRG prefix alone does not establish equivalence.
Editor's Note
Do not look for a COM number simply because the cable is described as a programming cable. With this model, check the Ethernet adapter and correct LAN port first. Selecting the wrong connection type can prevent discovery even with a healthy cable.
A broken RJ45 latch, darkened contacts or damage near the plug can cause intermittent connections under cabinet vibration. Release the latch and hold the connector housing when disconnecting.
If the link indicator is on but the software cannot connect, check the target IP, subnet mask, selected network adapter and COMMGR connection in sequence. A link indicator confirms the physical connection; it does not establish that the correct PLC is reachable.
Start with a known-good connection that follows the device manual. A cable tester can check conductor continuity and pair faults. Do not judge a used cable with replaced connectors by appearance alone.
A failed connection is not a reason to reset PLC network settings at random. Record the existing settings first and use the correct maintenance project and connection record where available. Check firewall permissions for the relevant software traffic as well.
Once communication is established, verify the connected CPU model and existing project backup before downloading a program. A healthy cable does not prove the open project belongs to that machine.
PDF manuals, wiring diagrams and software
Use our Delta PLC accessories PDF and software files page for cable and software documentation. General documents are available under Delta PLC and HMI manuals. For UC-PRG030-20A, read Figure 7 in the Delta PLC/HMI Cable Selection Guide together with the device's Ethernet section and the selected software's connection instructions.
Related subjects
DVP-SE · DVP12SE11R · DVP12SE11T · DVPEN01-SL · DVP-FEN01 · AH10EN-5A · Delta DOP-B
UC-PRG015-01A · UC-PRG030-01A · UC-PRG015-02A · UC-PRG030-02A · UC-PRG030-10A · UC-PRG020-12A · ISPSoft · WPLSoft · COMMGR · DCISoft
Navigation: Delta DVP programming cables · Delta PLC accessories · Delta DVP PLC series · Delta AS PLC series · Delta AH PLC series · Delta PLC models · Used Delta products · PDF and software files
External references
Delta PLC/HMI Cable Selection Guide – UC-PRG030-20A and Figure 7 · Delta DVP starter kit manual – RJ45 cable pin identification · Delta AS hardware and operation manual · Delta ISPSoft manual – COMMGR Ethernet connection