Delta DVP12SE11T – Ethernet PLC with 8 Inputs and 4 NPN Outputs
Delta DVP12SE11T is a DVP-SE main processing unit with 8 digital inputs and 4 NPN transistor outputs. With 16K-step program memory and 12K words of data registers, this PLC supports machine control, recipe management and network-based production monitoring.
Its distinguishing feature is the combination of mini USB, Ethernet and two RS-485 ports. Inputs are X0–X7; outputs are Y0–Y3. There is no built-in analog I/O; compatible DVP extensions add measurement and additional I/O functions.
Power supply and digital inputs
Supply: 24 V DC, operating range 20.4–28.8 V DC. CPU consumption is 1.5 W; external sensors and loads are additional. Size the power supply for the complete field load. The body is 37.4 mm wide and mounts on a 35 mm DIN rail inside a cabinet.
The S/S common determines sink/source input wiring. Connect S/S to 0 V for PNP sensors, or +24 V for NPN sensors. An NPN-output CPU does not restrict its inputs to NPN sensors.
For an inductive sensor, photoelectric sensor or limit switch, assess common wiring, signal level and response time together. The 2024 hardware sheet places X0–X2 in the 100 kHz input class and X3–X7 in the 10 kHz class. For an encoder, also check counter mode, A/B-phase evaluation and pulse widths.
Pulse outputs and NPN load wiring
Y0 and Y2 support up to 100 kHz; Y1 and Y3 up to 10 kHz. Pulse/direction or another pulse format depends on the instruction and receiver. Verify servo drive voltage and open-collector input compatibility; do not apply a 24 V field signal directly to a 5 V differential input.
Outputs are NPN open collector. Connect auxiliary power +24 V DC to UP and 0 V to ZP; connect the load between +DC and the corresponding Y output. Check CPU power and output auxiliary power separately. The output table specifies 5–30 V DC load voltage and a 0.5 A/point resistive-load limit; assess total load and switching conditions separately.
A transistor output is not a dry contact. Check coil current when selecting an interposing relay or contactor. Use appropriate diode/suppression circuitry and a suitable fuse for DC inductive loads; follow the manufacturer's grounding diagram.
Programming software and USB cable
WPLSoft or ISPSoft can program this CPU. Select the supported DVP-SE target in WPLSoft or ISPSoft. The Ladder project, CPU version and instructions must be compatible. Back up the existing project and important machine data before programming.
COM1 is the mini USB programming port. The manufacturer's cable guide lists UC-PRG015-01A – 1.5 m and UC-PRG030-01A – 3 m. Use an appropriate USB-to-mini-USB data cable. The SS2 model's 8-pin RS-232 programming cable does not connect to this port.
Install the appropriate Delta USB driver. For ISPSoft, create a USB driver in COMMGR and check device connection status. This is a different connection type from the UC-PRG020-12A USB-to-RS-232 cable driver.
Ethernet, factory IP address and DCISoft
The built-in Ethernet interface supports Modbus TCP. 12SE firmware V2.00 or later supports EtherNet/IP slave/adapter communication; check the firmware on a used CPU. Modbus TCP and EtherNet/IP are different protocols; select the correct driver and communication settings on the other device. Use an appropriate CAT-5e Ethernet cable or UC-PRG030-20A for the RJ45 connection.
Factory IP address: 192.168.1.5; subnet mask: 255.255.255.0. A used unit may have different settings. In DCISoft, select Ethernet communication and use Search to find the CPU; open its settings, edit network parameters and click Apply. Check the PC subnet and duplicate IP addresses on the network.
When connecting multiple PLCs/HMIs through an industrial switch, maintain an address record for every device. In an automation application, design recipe/counter update intervals alongside communication-loss behavior. An established Ethernet link alone does not prove that process data is handled correctly.
Two RS-485 ports, expansion and memory
COM2 and COM3 are RS-485 ports. Match RS-485 D+/D− polarity, station and Modbus ASCII/RTU format to the project. Arrange SG/shield connections and any required termination resistors according to the manufacturer's diagram.
Compatible left- and right-side extensions can be used; verify the special module's CPU/firmware support and power requirements. The SE series requires no battery; programs and latched data are stored in flash memory. Distinguish temporary registers from retained areas.
Related models
DVP12SE11R: 8 inputs and 4 relay outputs, with SE Ethernet and serial communication. Relay outputs cannot replace the fast pulse function.
DVP26SE11T: 14 inputs and 12 NPN transistor outputs, for SE applications requiring more onboard digital points.
DVP26SE11R: 14 inputs and 12 relay outputs. Select according to load type and switching frequency.
DVP14SS211T: An SS2 CPU with 8 inputs and 6 NPN outputs, without built-in Ethernet. Its communication and pulse capabilities differ, so it is not a direct equivalent.
Editor's Note
Check the complete label and T output suffix first. Before changing a used PLC, back up the application, important registers, IP address and serial-port settings.
If USB communication fails, check the data cable and COMMGR USB driver. For Ethernet, check the PC subnet and actual CPU IP; do not assume every used unit retains its factory address.
If an output LED illuminates but the load does not operate, measure UP/ZP power and voltage drop under load. Test all four outputs and check Y0/Y2 pulses with a suitable receiver or oscilloscope.
Perform a controlled power-loss test for recipes and production counters. Battery-free storage does not make every value retentive; verify restart behavior with the machine in a safe state.
Perform short-circuit checks with power isolated. Design the required safety relay and independent stopping arrangement for emergency stopping and protective functions.
For a used-unit sale, state quantity, label photographs, working/faulty condition and tests. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.
PDF documents and related topics
For wiring diagrams, USB and network settings, visit our Delta DVP PLC files page first. Use the DVP12SE11T row in the shared SE instruction sheet; do not assign the 26SE model's additional I/O to the 12SE.
Related topics and navigation: Delta and used models | Delta PLC | DVP PLC series | DVP-SE | DVP12SE11T model page
External references
Delta DVP-SE instruction sheet – 21 February 2024, DVP-0360030-02
Delta PLC/HMI Cable Selection Guide – SE, section 1.9.1
Delta DVP Starter Kit Manual – USB, COMMGR and Ethernet settings
Delta manufacturer page – DVP-SE features
Delta programming manual, Appendix B.5 – EtherNet/IP firmware and role