Delta UC-CMC030-01A

Delta UC-CMC030-01A 3-Metre CANopen Communication Cable

Delta UC-CMC030-01A is a 3-metre RJ45-to-RJ45 CANopen communication cable. It belongs to the Delta CANopen cables and Delta industrial network cables groups.

Compatible equipment and applications

The catalogue lists DVPCOPM-SL, DVP15MC11T, DVP15MC11T-06 and TAP-CN03. Verify the equipment code and designated CANopen port.

RJ45 identifies the connector format. Check the port label and equipment diagram; matching plug shapes do not establish electrical compatibility.

CANopen RJ45 pin assignments

The manufacturer's CANopen assignments are pin 1 CAN+, pin 2 CAN−, pins 3 and 7 CAN_GND, and pin 6 CAN_SHLD. Pins 4, 5 and 8 are reserved.

Read pin numbers against the plug's contact face and latch orientation. Two plugs drawn facing each other can show their numbers in opposite orders. Align connector viewing directions before measuring.

Termination and commissioning

Terminate the two physical ends of the CANopen bus. Delta specifies the TAP-TR01 terminator as 121 Ω. When using termination inside a distribution box, check its switch setting against its position on the bus.

The cable's 3-metre length does not define the permitted length of the complete network. Assess the total bus, branches and communication speed together. After connecting, verify node addresses and equipment communication settings.

Route the cable separately from motor and drive power wiring. Seat connector locks fully and leave the cable entries free of tension. Follow equipment installation instructions for shield and reference connections.

Other lengths in the same family

Shorter options: UC-CMC003-01A 0.3 m, UC-CMC005-01A 0.5 m, UC-CMC010-01A 1 m, UC-CMC015-01A 1.5 m, and UC-CMC020-01A 2 m.

Longer options: UC-CMC050-01A 5 m, UC-CMC100-01A 10 m, and UC-CMC200-01A 20 m. Account for the complete network length when selecting a cable for the route.

Editor's Note

Identify the correct port first. Adjacent RJ45 sockets inside a cabinet can perform different functions. If labels have worn away, use the equipment code to find its manual and establish the port's purpose.

Inspect latches and contacts on used cables. Broken locks, corrosion and crushed connector entries can interrupt communication under vibration. Comparing with a known working cable is a practical way to isolate the fault.

Disconnect power before electrical measurements. With both cable ends unplugged, check the required conductors for continuity and shorts. Do not apply high-voltage insulation testing while equipment remains connected.

Count termination points if the entire network fails. Trace the physical beginning and end of the bus and check for termination switches left enabled between them. Sketch the existing arrangement before adding resistors.

Inspect routing if faults occur only when a motor runs. Separate the cable from power wiring and repeat the test under the same operating conditions. Make one change at a time to distinguish cable, connection and configuration faults.

Verify more than communication LEDs after replacement. Secure the machine and check actual data exchange and command destinations. Record node addresses, speed settings and termination locations for later maintenance.

PDF diagrams and software

Use our Delta PLC accessories PDF and software files page for documentation. Consult Section 3.5, Figure 1 and Section 4.1, CANopen of the Delta PLC/HMI Cable Selection Guide. For configuration, use an equipment-supported CANopen Builder version and the relevant device documentation.