Delta AH06XA-5A

Delta AH06XA-5A analog module with 4 inputs and 2 outputs

The Delta AH06XA-5A combines 4 analog inputs and 2 analog outputs in one module for the Delta AH500 PLC. This AH analog module can receive 4–20 mA feedback from a pressure transmitter while sending a 0–10 V speed reference to a drive. For projects that require separate cards, see the AH04AD-5A analog input and AH04DA-5A analog output modules.

Input and output signal ranges

Voltage inputs and outputs support ±10 V, 0–10 V, ±5 V, 0–5 V and 1–5 V. Current inputs support ±20 mA, 0–20 mA and 4–20 mA. Current outputs can be set to 0–20 mA or 4–20 mA.

Hardware resolution is 16 bits, with a specified conversion time of 150 µs per channel. Voltage input impedance is above 1 MΩ, current input impedance is 250 Ω and the maximum current-output load is 550 Ω. For direct temperature sensor connections, use the AH04PT-5A for RTDs or the AH04TC-5A for thermocouples.

Terminal wiring and 24 V DC supply

The four analog inputs on the removable terminal block are marked CH0–CH3. For a voltage input, use the channel’s Vn+ and VIn− terminals. For a current input, bridge Vn+ to In+ on the same channel and connect the return to VIn−. For an output, select VO or IO according to the configured mode and use AG as the return.

The UP/ZP terminals require an external 24 V DC supply with a permissible range of 20.4–28.8 V DC. Check this field supply separately from the AH rack supply. Route analog cables away from power wiring and connect the shield to SG as shown in the manual. Use the full part number when selecting an AH external terminal or Delta PLC accessory.

ISPSoft channel configuration and data mapping

Install the module in a compatible AH expansion slot. In HWCONFIG within ISPSoft, select each channel’s signal type, range and scaling. Each channel uses two 16-bit data registers. The four inputs occupy 8 registers and the two outputs occupy 4 registers. Verify the starting addresses in the existing project. See Delta PLC software for related tools.

For example, a 4–20 mA transmitter scaled to 0–10 bar should read 5 bar at 12 mA. Compare the channel value in ISPSoft with the value displayed on the HMI.

Manuals and PDF files

AH500 Module Manual — English PDF. Chapter 4 covers AH06XA-5A channel configuration, scaling and online monitoring.

AH500 Hardware and Operation Manual — English PDF. See 2.7.1 for specifications, 4.9.7 for wiring and 5.4.2 for register mapping. Related documents are available in the Delta AH PLC PDF archive.

Editor’s Note

When buying used, check that the removable terminal block comes with the card. Inspect the terminal screws for corrosion and the rear backplane connector for bent pins.

Record each channel’s voltage or current mode before disconnecting the old module. Fit the Vn+ to In+ jumper only on current inputs.

If inputs and outputs both show problems, check the UP/ZP supply at the module terminals first. Then check the RUN and ERROR indicators.

On the bench, apply 4, 12 and 20 mA to a 4–20 mA input and compare the readings. Measure the output with a test load isolated from the machine and verify the drive’s input mode separately.

If several channels show noise, check the SG shield connection and the cable’s proximity to power wiring. Use an external signal isolator where the measurement requires channel-to-channel galvanic isolation.