Delta AH08DA-5C
Delta AH08DA-5C 8-Channel Analog Current Output Module
Delta AH08DA-5C is an eight-channel analog output module for Delta AH500 rack-based PLC systems. Each channel, CH0–CH7, can be set to 0–20 mA or 4–20 mA. The module converts a PLC speed, position or process reference into an analog current signal for a compatible drive, proportional valve or recorder input.
Wiring diagram and manuals
AH08DA-5C wiring diagram (PDF, English) · Printed page 4-72 of the AH500 Hardware & Operation Manual. See page 2-56 for current output specifications.
AH08DA-5C ISPSoft channel modes (PDF, English) · Printed page 3-27 of the AH500 Module Manual covers channel mode, calibration and scaling.
Output specifications and terminals
Hardware resolution is 16 bits, conversion time is 150 µs per channel, and maximum permissible load impedance is 550 Ω. Include the receiver input resistance, cable resistance and any other series elements in the loop.
On the removable terminal block, CH0 uses IO0 and AG, and CH7 uses IO7 and AG. Connect the 24 V DC auxiliary supply at UP/ZP as shown in the diagram. Route shielded signal cables away from power wiring and use SG for the shield connection as shown in the manual. The analog circuit is isolated from the digital circuit. There is no channel-to-channel isolation.
ISPSoft, channel modes and D registers
In HWCONFIG in ISPSoft, select 0 = disabled, 1 = 0–20 mA, or 2 = 4–20 mA. Match the software scaling to the receiver’s lower and upper range limits. For the PC connection, check the port supported by the CPU and the COMMGR profile. See the Delta PLC software section for setup information.
Each commanded output is a floating-point value stored in two 16-bit D registers. All eight channels occupy 16 D registers. For example, with start address D100, CH0 uses D100–D101 and CH7 uses D114–D115. Verify the actual start address in HWCONFIG.
Editor’s note
When buying a used module, check the full AH08DA-5C code on the label and make sure the removable terminal block is included.
On the bench, start with the UP/ZP auxiliary supply and the RUN/ERROR indicators. If all channels are unresponsive, check the supply and channel mode first.
In 4–20 mA mode, use a suitable test load and meter to check each channel at 4, 12 and 20 mA.
If the midpoint reading is off, check the PLC scaling and the receiver’s input settings first.
If only one channel is off, move the same test load to a known-good channel. This helps distinguish a faulty output from a terminal or wiring problem.
Model differences and related topics
For eight outputs, the AH08DA-5A supports voltage and current, the AH08DA-5B provides voltage outputs, and the AH08DA-5C provides current outputs. See the AH04DA-5A for four outputs or the AH06XA-5A for inputs and outputs on the same module.
To read analog measurements into the PLC, see the AH04AD-5A, AH08AD-5A, and AH08AD-5C input modules.
For rack planning, see AH expansion modules, AH power supplies, and Delta PLC accessories.