Delta AH04AD-5A
Delta AH04AD-5A 4-Channel Analog Input Module
The Delta AH04AD-5A is a four-channel, 16-bit analog input module for the Delta AH500 PLC. It converts voltage and current signals in 150 µs per channel and can connect pressure, flow and level transmitters to the PLC. See Delta AH analog modules for other configurations.
Input ranges and model selection
Voltage input ranges are 0–5 V, 1–5 V, ±5 V, 0–10 V and ±10 V. Current input ranges are 0–20 mA, 4–20 mA and ±20 mA. Set each channel’s input mode to match the connected transmitter.
For eight channels, the AH08AD-5A supports voltage and current, the AH08AD-5B supports voltage, and the AH08AD-5C supports current.
Terminal wiring and supply
The module uses a removable terminal block and an external 24 V DC supply. Delta specifies a supply range of 20.4–28.8 V DC. For a voltage input, use the channel’s Vn+ and VIn− terminals. For a current input, fit the jumper between Vn+ and In+ on that channel as shown in Delta’s wiring diagram. See AH power supplies for supply selection.
ISPSoft, addressing and scaling
Add the module to its rack slot in HWCONFIG in ISPSoft. Set the input mode and digital scaling range for each channel. The module occupies two data words per channel, for a total of eight input data words. For example, with a linear 4–20 mA transmitter scaled to 0–10 bar, 12 mA represents 5 bar. See AH expansion modules and Delta PLC software for rack and engineering information.
Manual and wiring diagram
AH04AD-5A analog input wiring diagram · English AH500 Module Manual. Specifications are on PDF pages 28–30, wiring on page 43, and initial ISPSoft setup on pages 45–47. Browse the series documentation under Delta AH PLC PDF files.
Editor’s Note
When buying used, verify the AH04AD-5A nameplate and check that the removable terminal block is included.
Test all four channels in turn with a known signal source.
For a 4–20 mA test, monitor the PLC reading at 4, 12 and 20 mA.
If the reading is off, check the channel mode, current-input jumper and scaling first.
If the signal fluctuates when a drive runs, check the shield connection and the distance between analog and power cables.
Related topics
For inputs and outputs in one module, see the AH06XA-5A. For analog outputs, see the AH04DA-5A, AH08DA-5A, AH08DA-5B and AH08DA-5C. For direct RTD and thermocouple measurements, see AH temperature modules.