The Delta AH04DA-5A is a four-channel, 16-bit analog output module for the Delta AH500 PLC. Each channel can be configured independently for voltage or current output. Conversion time is 150 µs per channel. This AH analog module provides analog signals such as speed references for AC drives and position references for proportional valves.

Output ranges and load limits

Voltage output: ±10 V, 0–10 V, ±5 V, 0–5 V or 1–5 V.
Current output: 0–20 mA or 4–20 mA.
The maximum total load in current mode is 550 Ω. Delta specifies a load impedance of 1 kΩ–2 MΩ in ±10 V and 0–10 V modes.

Terminal wiring and auxiliary supply

Use the channel’s VO–AG terminals for voltage output and IO–AG for current output. For example, CH0 voltage output uses VO0–AG and CH3 current output uses IO3–AG. Connect the module’s 24 V DC auxiliary supply to UP and ZP. Follow the manual’s SLD–SG wiring diagram for cable shielding. See AH power supplies for rack supply options.

ISPSoft channel settings and scaling

In ISPSoft, use HWCONFIG to select the output mode and scaling for CH0–CH3. On the AH04DA-5A, for example, mode 2 selects 0–10 V and mode 7 selects 4–20 mA. The module uses two D registers per channel, eight in total. Check the start address in the project. For programming, use the PLC cable and COMMGR settings that match the CPU port.

PDF and wiring diagram

All Delta AH PLC PDF files

AH04DA-5A wiring diagram (English, printed page 4-70) · ISPSoft channel modes and scaling (English, printed page 3-27).

Editor’s Note
On a used module, check the full model code, removable terminal block and backplane connector.
Bench-test the module independently of the machine and measure the UP/ZP auxiliary supply first.
On a 0–10 V channel, verify 0, 5 and 10 V at the low, midpoint and high commands.
On a 4–20 mA channel, repeat the test at 4, 12 and 20 mA with a suitable test load.
If a channel passes on the bench but drifts in the field, check the receiver input mode, total load and cable shield.

Related topics

Eight-output options include the voltage-and-current AH08DA-5A, voltage-output AH08DA-5B and current-output AH08DA-5C. For four analog inputs and two analog outputs, see the AH06XA-5A.

Analog input modules for measurement include the AH04AD-5A, AH08AD-5A, AH08AD-5B and AH08AD-5C.

AH expansion modules · Delta AH PLC series · Delta PLC accessories · Delta PLC · Second-hand Delta models

External reference · Delta AH hardware manual and module specifications