Delta AH32AN02P-5B

Delta AH32AN02P-5B – 32-Point PNP Digital Output Module, DB37

The Delta AH32AN02P-5B is a rack-mounted module with 32 PNP transistor outputs for the Delta AH500 PLC. Field wiring connects through the front DB37 connector. In the Delta AH digital module range, this model suits panel layouts that bring the field wiring to an external terminal block.

PNP outputs and load limits

When a PNP output turns on, the Y terminal supplies positive voltage to the load. The model-specific wiring diagram specifies 12–24 VDC. For resistive loads, Delta specifies limits of 100 mA per output and 1 A per common (COM). Follow the manual’s 24 VDC auxiliary supply diagram for UP and ZP. See AH power supplies when calculating the panel’s power requirements.

For a coil or a load with high inrush current, select an interposing relay or driver interface rated for that load. The stated per-output current limit applies to resistive loads.

DB37 cable and external terminals

Delta specifies the UC-ET010-33B 1 m DB37 cable between the module and the external terminal block. Earlier documentation also lists it as DVPACAB7C10. The UB-10-OT32B / DVPAETB-OT32B brings the transistor outputs to field terminals. For applications that require relay contacts, Delta lists the UB-10-OR32B / DVPAETB-OR32B relay terminal module. Check its own documentation for the contact load ratings.

For other AH I/O cables and AH external terminals, match the accessories to the full module part number.

ISPSoft addressing and related models

Select the module’s rack and slot in HWCONFIG within ISPSoft. The module uses 32 consecutive Y bits. If the start address is Y0.0, the outputs occupy Y0.0–Y0.15 and Y1.0–Y1.15. On an existing machine, check the actual start address in the project. Use COMMGR to check the PC-to-PLC connection.

The AH32AN02P-5A is the PNP model with a removable terminal block, and the AH32AN02P-5C is the PNP model with a 40-pin latch connector. The AH32AN02T-5B uses the same DB37 connector type and has NPN outputs. The AH32AN02T-5A is the NPN model with a removable terminal block.

Manual and PDF downloads

Delta AH500 Hardware and Operation Manual (PDF, English). See PDF page 67 (printed 2-31) for the specifications, pages 220–221 (4-50–4-51) for module and terminal wiring, and page 301 (5-13) for Y addressing.

See the Delta PLC/HMI Cable Selection Guide, Section 2.2.5 for the cable and terminal options. Other manuals are available in the Delta AH PLC PDF files archive.

Editor’s Note

When buying a spare, check the side label for the complete AH32AN02P-5B part number.

Inspect the DB37 pins, retaining screws and both ends of the cable.

If the Y LED is on and there is no field output, check the UP/ZP auxiliary supply first, then the cable and terminal block.

On the bench, test outputs from both Y address groups using a known resistive load.

Before removing the original module, record the first Y address and whether the panel uses the OT32B or OR32B terminal.

Related topics

What is a PLC? · Used digital I/O modules

More in this range · Delta AH PLC series · AH expansion modules · Delta PLC models · Used Delta equipment

External references

Delta AH500 Hardware and Operation Manual, distributor archive (PDF)