Delta AH15EN-5A
Delta AH15EN-5A – IEC 60870-5-104 and Modbus TCP Ethernet Module
The Delta AH15EN-5A is a rack-mounted Ethernet communication module for the Delta AH500 PLC. It has two 10/100 Mbit/s RJ45 ports and supports Modbus TCP client and server operation. IEC 60870-5-104 requires module firmware V2.00 or later.
The AH15EN-5A transfers PLC field data to a SCADA system or remote station over Ethernet. When comparing Delta AH communication modules, check the peer device’s protocol and client or server role alongside the data addresses in the PLC.
Two Ethernet ports and IP operating modes
In switch mode, the two RJ45 ports operate as a built-in switch and the module uses one IP address. With the switch function disabled in HWCONFIG, each port can use its own IP address and subnet mask to connect to a separate network. Use the site’s Ethernet topology and IP addressing plan to select the operating mode.
The ports support Auto-MDI/MDIX and automatic 10/100 Mbit/s speed detection. Delta specifies a 100 m maximum link length with Cat 5e cable. See industrial network cables for cabinet wiring. Before adding a module, check the rack, slot and available AH power supply capacity.
Modbus TCP and IEC 60870-5-104 configuration
Delta’s module manual lists maximums of 64 client connections and 128 server connections for Modbus TCP, and 16 client connections and 16 server connections for IEC 60870-5-104. During IEC 104 commissioning, compare the common ASDU address, information object addresses (IOAs) and PLC memory mapping with the peer station’s point list.
Add the module to the correct rack and slot in HWCONFIG within ISPSoft. Configure the module’s IP operating mode and protocol parameters there. Use COMMGR for the PC-to-PLC connection channel and see Delta PLC software for engineering tool versions.
How the AH15EN-5A differs from related models
The AH10EN-5A is documented for Modbus TCP and EtherNet/IP projects. The AH15EN-5A is intended for projects that require Modbus TCP and IEC 60870-5-104. For an Ethernet remote I/O station, see the AHRTU-ETHN-5A. For serial communication, see the AH10SCM-5A for RS-485/RS-422 or the AH15SCM-5A for RS-232.
Manual and PDF downloads
Delta AH500 Module Manual (PDF, English). See PDF page 345 (printed 9-2) for firmware and port specifications, page 350 (9-7) for single- and dual-IP modes, and page 375 (9-32) for IEC 60870-5-104 parameters.
See the Delta AH PLC PDF files archive for other documents in the series.
Editor’s Note
When buying a used module, ask for a nameplate photo and the firmware version. Confirm V2.00 or later if you need IEC 104.
Before removing the original module, save the HWCONFIG project and record the port mode and IP addresses.
A lit link indicator confirms a physical connection. Read a known data point to check application communication.
If IEC 104 connects and no data arrives, compare the common ASDU address, IOA list and PLC memory mapping.
If both ports are used, bench-test each RJ45 port individually on a network separate from production.
Related topics
EtherNet/IP and Modbus TCP compared · EtherNet/IP and standard Ethernet · Used communication modules
More in this range · Delta AH PLC series · AH expansion modules · Delta PLC models · Used Delta equipment
External references
Delta AH500 Module Manual, Chapter 9 (distributor copy of the manufacturer’s manual)