6ES5 525-3UA21

Siemens SIMATIC S5 CP 525-2 — 6ES5 525-3UA21

The Siemens 6ES5 525-3UA21 is the CP 525-2 serial communications processor for S5-115U, S5-135U, S5-150U and S5-155U systems. This S5 communications module has two 25-pin serial sockets. Both IF1 and IF2 support V.24 (RS-232-C) or 20 mA TTY. The manual specifies 110–19,200 baud, with TTY limited to 9,600 baud.

The card connects a SIMATIC S5 CPU to another PLC, a host computer or a PT88/PT89 printer. For example, an RK 512 link can send a PLC data block to a partner station. In a printer application, the CP uses message text loaded through COM 525.

Connecting IF1 and IF2

Both ports use asynchronous serial transmission. Match the connection cable and COM 525 setup to the selected electrical interface, V.24 / RS-232-C or 20 mA TTY. A programming device can connect to IF2 over TTY. Before selecting the TTY cable, establish whether the CP or the partner supplies loop current.

Siemens specifies up to 20 m for V.24 and up to 1 km for TTY at 9,600 baud. The manual calls for a shielded cable with metal connectors and shield grounding at both ends. Match the baud rate, character length, parity and stop-bit settings at both ends.

RK 512, 3964R and configuration memory

RK 512 defines the telegrams used for read and write jobs. 3964 or 3964R handles their transfer over the serial link. For RK 512 operation at 19,200 baud, Siemens specifies V.24 with only one port loaded and in service. Check the SEND, FETCH and RECEIVE jobs in the STEP 5 program against the COM 525 configuration.

Port drivers and user settings are stored on a plug-in S5 memory submodule. Siemens lists the 6ES5 373-0AA41 EPROM or 6ES5 377-0AB21 RAM for the S5R006 driver. A documented setup using the 377 RAM also uses the 6ES5 980-0DA11 backup battery. Check the installed memory type and back up the configuration before removal.

Rack, power and interface addressing

For the S5-115U, Siemens lists slots 0–5 in the CR 700-2 rack. The ER 701-3 and the CR 700-3 arrangement shown in the manual require IM 304 and IM 314. On the S5-135U, S-type processors are excluded. Check the slot chart for the S5-150U or S5-155U rack in use. Siemens specifies fan cooling, a 5 V (±5%) supply at up to 2.1 A and 24 V for the TTY current source.

The JB 16 jumpers set the even logical address of IF1. IF2 takes the next odd number automatically. With IF1 at 12, IF2 is 13. The SSNR parameter in the STEP 5 handling block must match the selected interface number.

Port LEDs and related processors

When troubleshooting, read each port LED together with the RUN/STOP/PGR selector. A red LED can indicate STOP/PGR, a missing port driver or a startup issue. The CP 525 6ES5 525-3UA11 is a separate version. When assessing the CP 524 6ES5 524-3UA13 or the CP 544 6ES5 544-3UA11 for a replacement, compare the port count, electrical interface and driver file.

Editor’s note

Label. Record the full 6ES5 525-3UA21 order number, the hardware revision if marked and the memory submodule label.

Ports. Label the IF1 and IF2 leads. Record the partner device, electrical interface and serial settings for each port.

Jumpers. Photograph the JB 16 settings. Check SSNR and the job numbers in the CPU program.

Backup. Save the COM 525 project and driver files before removing the CP or memory submodule. Isolate the power before removing or inserting either component.

First check. If a port LED stays on in RUN, check the loaded driver and startup status first, then the partner cable and serial settings.

OtomasyonAVM resources and PDFs

SIMATIC S5 communications modules · S5-135U central rack and manual page · S5-135U/155U central unit and system manual

OtomasyonAVM Siemens S5 PDF archive

Related topics

CP 525 6ES5 525-3UA11 · CP 524 6ES5 524-3UA13 · CP 544 6ES5 544-3UA11 · 6ES5 373-0AA41 EPROM

Back to the S5 range

S5 communications modules · SIMATIC S5 modules · Siemens SIMATIC S5

If you have a CP 525-2 to sell, send a label photo, quantity and operating condition to otomasyonavm@gmail.com.

Siemens and external references

Siemens COM 525 Volume 1 — CP 525-2 hardware and installation (English copy) · CP 525-2 IF1 and IF2 pin assignments (German)

Siemens COM 525 Volume 2 — programming and RK 512 example (German) · Siemens S5R006 — 3UA21 driver and memory requirements (German)

Siemens S5 migration guide — 6ES5 525-3UA21 compatibility entry