6ES5 980-0DA11

Siemens 6ES5 980-0DA11 — lithium backup battery for RAM memory submodules

Siemens 6ES5 980-0DA11 is a RAM memory submodule backup battery for Siemens S5 equipment. The Siemens ST 50 catalogue lists this part as 3 V / 0.2 Ah (200 mAh). In SIMATIC S5 maintenance, it supports data retention in a battery-backed RAM submodule outside the CPU.

The S5-135U/155U system manual lists it with the 6ES5 377-0BA31 memory submodule and identifies the cell as a CR 2430 (LF-1/2W) lithium button cell with terminal lugs. Match the connection arrangement as well as the cell designation when ordering.

Selection and differences between order numbers

6ES5 980-0MB11 and 6ES5 980-0NC11 are different order numbers. Do not select them interchangeably under a general “S5 battery” description. Record the battery or rechargeable unit in the S5 power supply separately from the RAM battery. Verify voltage, terminals, polarity and installation location together.

This part does not turn RAM into EEPROM or Flash memory. Replacing a battery does not restore an erased program. Include a current PLC program backup, a means of reloading it and a check of the existing memory contents in the maintenance plan.

CPU and memory revision checks

Record the complete processor number, such as CPU 922-3UA11, CPU 928-3UA12 or CPU 928B-3UB12. Keep different versions such as the CPU 928-3UA21 and CPU 928B-3UB21 distinct in the maintenance record. For the battery order, also use the installed RAM number and a photograph of the existing battery connection rather than deciding from the CPU family name alone.

Connection and maintenance preparation

Back up first. Set the CPU to STOP and switch off PLC power before removing or inserting the RAM submodule. Fit the replacement with correct polarity at its screw terminals. Photograph and mark the connections before removal rather than relying on their appearance.

When recording the rack layout, identify interface modules and communication processors by their labels as well. State exactly which memory received the battery; this helps prevent the wrong component being replaced during later maintenance.

During PLC troubleshooting, do not make a battery-voltage reading the only acceptance criterion. Consider contact condition, memory contents and the result of a controlled restart together. Plan any power-interruption test after verifying the backup and preparing a recovery method.

Editor’s note

When buying used Siemens equipment, do not assume an old battery supplied with the board is serviceable. A working board and remaining battery life are separate questions. Read the full marking and any date information first.

Before fitting the replacement, make a program backup and check that you can open it. A quick battery change is no reason to risk the only copy. A new cell cannot recover a program that has already been lost.

Matching the button-cell diameter is only part of the check. The terminal-lug direction and screw positions must fit too. Do not accept bent terminals, a forced fit or temporary wiring as a permanent repair.

Photograph corrosion, cracks or loose contacts around the battery and assess the connection first. A new cell in a faulty connection does not complete the job. Do not recharge the lithium cell or short its terminals.

Record the replacement date and battery identification. “Battery changed” alone gives the next technician little to work with. Include the RAM number and checks actually performed in the same record.

For legacy S5 installations, the verified machine program and a clear maintenance record are particularly valuable. Record the outcome of controlled checks, and distinguish completed tests from power-interruption or retention tests that have not been performed.

OtomasyonAVM resources and PDFs

+ Siemens S5 PDF archive: system and memory documentation. Manufacturer references for this battery are at the end of this page.

+ 6ES5 980-0DA11 model page and second-hand Siemens S5 models: the product and related system parts.

Related topics

+ S5 memory submodules · 6ES5 980-0MB11 · 6ES5 980-0NC11: memory products and different battery order numbers.

+ PLC programming and PLC debugging: backup and maintenance preparation.

Browse SIMATIC S5

Product page · Siemens S5 · S5 memory products · Used Siemens equipment

Siemens and external references

+ Siemens ST 50 — 1998 catalogue, English; manufacturer document hosted by Acomee. Printed page 4/156 lists 6ES5 980-0DA11 for RAM submodules at 3 V / 0.2 Ah.

+ Siemens S5-135U/155U System Manual — 6ES5 998-0SH21, Edition 07, 11/1999. Section 5.10: 377 submodules; page 5-91: cell type; Appendix A-4: ordering association.