6ES5 544-3UA11
Siemens 6ES5 544-3UA11 CP 544 Serial Communications Processor
Siemens 6ES5 544-3UA11 is the CP 544 point-to-point serial communications processor for SIMATIC S5 S5-115U/H, S5-135U and S5-155U/H controllers. It has two serial device ports, SI1 and SI2, each fitted with a plug-in interface submodule, and a separate PG port. It supports up to 76.8 kbit/s over RS-422-A. Built-in protocols are RK 512, 3964/3964R and the Open Driver.
The CP 544 exchanges PLC data with a computer or another controller. On an existing link to a CP 524 or CP 525-2, match the physical interface and protocol at both ends. Siemens specifies the 6ES5 544-3UB11 CP 544B for loadable special drivers.
Interface options for SI1 and SI2
Select an interface submodule for each device port. The 6ES5 752-0AA22 supports up to 19.2 kbit/s over V.24/RS-232C. The 6ES5 752-0AA12 supports up to 9.6 kbit/s on a 20 mA TTY current loop. The 6ES5 752-0AA42 and 6ES5 752-0AA43 support up to 76.8 kbit/s in RS-422-A mode.
The 0AA42 requires a fan assembly. The Siemens manual supplement permits fanless operation with the 0AA43. For RK 512 and 3964/3964R, set the differential submodule to RS-422-A mode. The combined rate of both ports must stay within 76.8 kbit/s with these protocols. With the Open Driver, count a full-duplex port at twice its configured rate.
When checking S5 serial cables, distinguish the 6ES5 726-1BF00 TTY cable from the 6ES5 726-8BC00 V.24 cable. Verify the active and passive ends on a TTY loop and the transmit and receive pairs on RS-422-A. Terminate the cable shield according to Siemens’ grounding and shielding instructions.
Rack slots, addressing and COM PP setup
Select an approved slot for the rack from Table 2.2 of the manual. The CR 700-2 and ER 701-3 require an adapter casing. Siemens’ S5-115U application example uses a 6ES5 491-0LA12 adapter casing, a CPU 944 and a PS 951 7LD12 power supply. The CP draws up to 0.9 A from the 5 V rail without submodules.
SSNR is the CP page number addressed by the STEP 5 handling blocks. Even page numbers select SI1 and odd numbers select SI2. Use COM PP to configure the port protocol, serial settings and job numbers. For RK 512, use the same SEND/FETCH job number in the STEP 5 block and COM PP. Check the partner’s data block address separately.
Editor’s note
When ordering a spare, ask for a photo of the 3UA11 label and the complete part number of each submodule fitted to SI1 and SI2.
Back up the COM PP project before removing the CP. Parameters held only in internal RAM are lost when the card is withdrawn.
Isolate the rack and verify that it is de-energized before removing the CP. Match the page address switch settings and the submodule jumpers on the replacement.
If TXD flashes slowly in red, check CPU-to-CP synchronization first. Review the STEP 5 SYNCHRON call and its SSNR setting.
If the CP is in RUN but the partner does not reply, compare the serial interface type, baud rate and parity at both ends. Then read the ANZW status word and the SYSTAT entry in COM PP.
OtomasyonAVM resources and PDFs
+ About the Siemens SIMATIC S5 PLC
+ SIMATIC S5 manuals and PDF archive
+ SIMATIC S5-115H system manual (PDF)
Related topics
+ 6ES5 544-3UB11 CP 544B · 6ES5 524-3UA15 CP 524 · 6ES5 525-3UA21 CP 525-2
Browse the range
+ S5 communications modules · SIMATIC S5 · Used Siemens automation equipment
Siemens and external references
+ Siemens CP 544 manual · 6ES5 998-2DB21 (PDF) · Supplement on 0AA43 fan requirements and CP 544B
+ Siemens 6ES5 544-3UA11 data sheet (PDF)
+ Siemens S5 to S7-1500 serial communications application example (PDF)