6ES5 544-3UB11
Siemens 6ES5 544-3UB11 SIMATIC S5 CP 544B Communications Processor
The Siemens 6ES5 544-3UB11 is a CP 544B serial communications processor for SIMATIC S5 S5-115U/H, S5-135U (excluding the S processor), and S5-155U/H systems. It handles point-to-point data exchange between the PLC and a connected device. It has two configurable device ports, SI 1 and SI 2, and a separate PG programming port. The interface determines the maximum line rate, up to 76,800 baud on RS-422-A, 19,200 on RS-232C, and 9,600 on TTY.
Typical uses for this S5 communications module include PLC-to-PLC links and connections to computers or serial barcode readers. Built-in options include RK 512, 3964/3964R, and the open driver (ASCII). The -3UB11 B version adds support for loadable special drivers, such as Modbus RTU, to the functions of the 6ES5 544-3UA11 CP 544.
Which interface fits SI 1 and SI 2?
Each device port takes a SIMATIC S5 752 interface submodule matched to the electrical interface at the other end. Siemens lists the 6ES5 752-0AA12 for 20 mA TTY current loop, the 6ES5 752-0AA22 for V.24/V.28 (RS-232C), and the 6ES5 752-0AA43 for RS-422-A/RS-485.
The built-in protocols use the differential submodule in four-wire RS-422-A mode. For two-wire RS-485, check that the selected driver supports it. Siemens permits fanless operation with the -0AA43. The manual specifies forced ventilation for the earlier 6ES5 752-0AA42.
Match the S5 serial cable to the devices and pin assignments at both ends. CP-to-CP cable examples include the 6ES5 726-1BF00 TTY cable and the 6ES5 726-8BC00 V.24 cable. For a PG connection, Siemens lists the 6ES5 734-2BF00 connecting cable with the 6ES5 734-4AG00 adapter.
How are the protocols and ports configured?
The two ports can run different protocols. With RK 512 or 3964/3964R, the combined line rate is limited to 76,800 baud. With the open driver and both ports in full-duplex mode, the combined limit is 38,400 baud. Use COM PP to match the protocol, line rate, parity, data bits, and stop bits to the connected device.
Special drivers require COM PP V3.0 or later and a user memory card. Siemens catalog options include the 256 KB 6ES5 374-2KH21 flash EPROM and 256 KB 6ES5 374-2AH21 RAM card. For example, the 6ES5 897-3KB11 driver lets the CP 544B operate as a Modbus RTU master.
Where does the CP fit and how is the link checked?
Use the full S5 rack order number to look up the permitted slots in the installation table. In S5-115U/H installations, the CR 700-2 and supported ER 701-3 configurations require an adapter casing. The CR 700-3 has its own slot list. Siemens lists the 6ES5 491-0LB11 adapter casing for these racks.
Check the slot lists separately for the S5-135U/155U central controller and the EU 185U expansion unit in an S5-155H. Switch off rack power before inserting or removing the CP, an interface submodule, or a memory card.
CPU-to-CP data exchange uses a SYNCHRON call and the appropriate SEND/RECEIVE blocks in STEP 5. When troubleshooting, check the CP’s RUN/STOP state first, then the port’s TXD/RXD indicators and COM PP diagnostics. TXD/RXD indicate job status. Check the cable and the connected device separately to verify the physical link.
Editor’s note
Read the -3UB11 suffix and hardware revision from the replacement module’s label. Siemens confirms that revision 5 is compatible with revision 4. S3 and the jumpers are no longer required for that changeover.
Label the SI 1 and SI 2 cables before removing the existing module. Record the interface submodule numbers, the rack slot, and the positions of S2, S4, and S5.
Back up the COM PP parameter set and any special driver file. When sourcing spares for a system with a special driver, verify the CP, interface submodule, and memory card individually.
If one port drops out after replacement, start with that port’s pinout, settings, and connected device. If both ports fail, also check whether the CPU and CP have synchronized.
If the cabinet has an older serial link built around a CP 524 or CP 525, record the full cable part number and the installed protocol. Use those details and the existing STEP 5 calls to check whether the replacement fits the application.
OtomasyonAVM resources and PDFs
For module families and hardware, see SIMATIC S5 communications modules and the Siemens S5 PLC overview.
SIMATIC S5-115 PDF archive and SIMATIC S5-115H system manual (English PDF).
Related topics
CP 544 6ES5 544-3UA11, CP 524 6ES5 524-3UA15, and CP 525 6ES5 525-3UA21.
Browse SIMATIC S5
SIMATIC S5 family › S5 communications modules
External references
Siemens CP 544 manual (English PDF) · Siemens CP 544 and CP 544B hardware revision note (German/English PDF).
Siemens CP 544 manual with CP 544B supplement (German PDF) · Siemens CP 544B Modbus RTU master driver guide (German PDF).