6ES5 304-3UA11
Siemens 6ES5 304-3UA11 — IM 304 Distributed Expansion Interface
6ES5 304-3UA11 is an IM 304 expansion interface installed in a SIMATIC S5 central controller. Working with an IM 314-3UA11 at the expansion end, it extends the S5 bus through a symmetrical connection over up to 600 m.
The exact-code specification in the Siemens S5-115U manual states 1.5 A maximum consumption from the internal 5 V supply and an approximate 0.3 kg weight. Check power-supply capacity and the rack arrangement against this load. Its function is to link the central controller to remote I/O equipment.
Two connection branches and system arrangement
IM 304 provides two symmetrical interfaces, each supporting up to four expansion units. The 600 m limit applies to the total branch from IM 304 to the last IM 314. Assess the expansion arrangement against the module configurations permitted by the CPU and rack.
The S5-115U manual describes connections to ER 701-2/701-3 and EU 183/185/186. If CP communications cards or IP intelligent modules are required, verify rack and addressing support separately. IM 304/314 is used in distributed arrangements that support these module types.
721 cable and line termination
The link uses 721-0 series S5 connecting cables. Example lengths are 721-0BB00 — 1 m, 721-0BB60 — 1.6 m, 721-0BC50 — 2.5 m and 721-0BD20 — 3.2 m. Compare the complete cable code, connectors and shielding with the installed arrangement.
Fit a 6ES5 760-1AA11 terminating plug to the lower front X4 socket of the last standard IM 314 on each branch. Also check the mechanical arrangement of the 491-0LA12 adapter casing listed for IM 314 in S5-115U installations.
Switches and jumpers on the UA11 version
On the IM 304-3UA1. family, cable length is selected using jumper block X12. The manual shows 100/250/450/600 m settings, based on the longest branch connected to X3 or X4. If an IP or CP is installed in the expansion unit, the manual requires the longest-distance setting regardless of the actual cable length.
For distributed connection, all S3 switches are ON; S1/S2 must also be ON for an interface that is used. Check X11 operating jumpers and X14/X15 status evaluation against the UA-specific drawing. When considering 304-3UA12 or 304-3UB11, compare the complete code and board arrangement; do not copy the UB cable-length setting directly to UA11.
Grounding and functional checks
The potential difference between central controller and expansion unit must not exceed 7 V; provide suitable equipotential bonding. During fault investigation, check supply, shielding, connector locks, termination and jumper settings in order. Monitor I/O conditions with the machine in an appropriate safe condition.
When selecting a used module, check the full label, hardware revision and operation of both connection branches. Before removal, preserve the program/memory backup, jumper photographs and wiring drawings for the existing S5 system.
Editor’s note
Give the UA11 suffix a careful look. Different board arrangements carry the IM 304 name. A clear photograph and the matching manual can save a great deal of unnecessary fault-finding.
If the connection is missing, check the basics before blaming the card. Look at both supplies, cable ends and the final terminating plug. A loose connector lock can silence an otherwise healthy system in an ageing panel.
Do not choose a length setting by guesswork. Trace where the cable runs and where it ends, then select the appropriate setting. Remember the manual’s special length rule when an IP or CP is fitted.
Photograph every jumper and switch before removing the original card. A working replacement may arrive configured for a different machine, so make sure its settings belong to your installation.
For a used module, look beyond a clean front plate. Inspect both sockets, backplane connections and the hardware revision. Where possible, test both branches on suitable equipment; a little preparation helps when maintenance is due.
OtomasyonAVM resources and PDFs
+ OtomasyonAVM S5 PDF archive · About Siemens S5 PLCs. For 304-3UA11, the main references are S5-115U manual pages 3-22–3-24 and 15-61.
Related topics
+ 314-3UA11 counterpart interface · 760-1AA11 terminator · 721 connecting cables · 304-3UA12 · 304-3UB11. Verify the exact revision and application rules separately.
Browse SIMATIC S5
+ S5 interface modules · S5 expansion hardware · SIMATIC S5 · Siemens second-hand equipment.