6ES5 524-3UA13
Siemens 6ES5 524-3UA13 CP 524 Serial Communications Processor
Siemens 6ES5 524-3UA13 is the CP 524 serial communications processor for SIMATIC S5 S5-115U, S5-135U, S5-150U and S5-155U controllers. It has one device interface that accepts a plug-in submodule for V.24/RS-232C, 20 mA TTY or RS-422. The CP 524 manual specifies up to 19.2 kbit/s for V.24 and RS-422-A and 9.6 kbit/s for TTY.
The CP 524 transfers PLC data to a computer or another controller. An RK 512 link can use either the 3964 or 3964R transmission procedure. The CP 525 and CP 525-2 are separate models with two device interfaces. When comparing this card with the CP 544, check the port count and the existing communications project.
Interface submodule, cable and driver
The plug-in interface submodule fits the lower front receptacle. The 6ES5 752-0AA12 is TTY, the 6ES5 752-0AA22 is V.24/RS-232C, and the 6ES5 752-0AA42 is the RS-422-A/RS-485 type. Siemens’ S5R01E driver uses the differential submodule in RS-422 mode and limits the line rate to 50–9,600 baud. If evaluating a 6ES5 524-3UA15, verify that order number and its fitted submodule separately.
Select the S5 connection cable using the pinout for each end. For TTY, check which device supplies loop current. For RS-422, verify the transmit and receive pairs. Follow Siemens’ shielding and grounding instructions when terminating the screened data cable.
Rack slots, SSNR and EPROM
The permitted slot depends on the S5 rack. On an S5-115U with a CR 700-2 subrack, select an approved slot from the manual. Siemens requires a fan for the listed CP 524 installations. The manual specifies a maximum of 1.5 A on the 5 V rail for the CP 524 with its plug-in interface arrangement. The TTY submodule draws 60 mA from the 24 V rail.
The application created in COM 525 resides in the EPROM memory submodule in the upper receptacle. Siemens lists the 6ES5 373-0AA41 and a suitable 6ES5 752-0AAx2 interface submodule for S5R01E on the 3UA13. The interface number set by jumpers on the board must match SSNR in the STEP 5 handling blocks.
Editor’s note
When sourcing a used unit, ask for separate photos of the 3UA13 label, serial interface submodule and EPROM. Confirm which parts are included.
Before replacing the card, save the COM 525 project files and record the EPROM label and SSNR setting.
Isolate the rack and verify it is de-energized before removing or installing the CP, interface submodule or EPROM.
If IF1 is lit, check the RUN/STOP selector first. If it stays lit in RUN, follow the manual’s startup and EPROM diagnostics.
If the CP is in RUN but the partner does not respond, compare the serial interface standard, rate, parity and 3964/3964R selection at both ends.
OtomasyonAVM resources and PDFs
+ About the Siemens SIMATIC S5 PLC
+ SIMATIC S5 manuals and PDF archive
Related topics
+ 6ES5 524-3UA15 CP 524 · 6ES5 525-3UA21 CP 525-2 · 6ES5 544-3UA11 CP 544
Browse the range
+ S5 communications modules · SIMATIC S5 · Used Siemens automation equipment
Siemens and external references
+ Siemens 6ES5 524-3UA13 data sheet (PDF)
+ Siemens S5R01E driver note · 3UA13 hardware requirements (German PDF)
+ Siemens COM 525 manual · Volume 1, CP 524 hardware and RK 512 · Siemens COM 525 manual · CP 524 technical data (German PDF)