6ES5 470-8MD12

Siemens 6ES5 470-8MD12 | SIMATIC S5 470 Analog Output Module, 2 × 1–5 V

The Siemens 6ES5 470-8MD12 is a SIMATIC S5 analog output module that converts PLC command words into two 1–5 V analog voltage outputs. It is used with S5-90U, S5-95U and S5-100U PLCs and with ET 100U and ET 200U distributed I/O stations. The outputs are galvanically isolated from each other and from ground. The nominal field supply is 24 V DC and the minimum load resistance is 3.3 kΩ per channel.

In service, the module sends a setpoint to a valve positioner or an analog signal controller with a 1–5 V input. The command runs from 1 V at the low end to 5 V at full scale. The related 6ES5 470-8MD11 uses the same analog voltage range. Siemens lists a module delay of 0.10 ms for the 8MD11 and 0.15 ms for the 8MD12 in its ET 200U tables.

Output range and STEP 5 scaling

The 8MD12 has a nominal range of 1–5 V. Other versions in the series include the 6ES5 470-8MA12 for ±10 V, the 6ES5 470-8MB12 for ±20 mA and the 6ES5 470-8MC12 for 4–20 mA. Match the receiving device’s input range to the full order number when selecting a replacement.

Siemens specifies an 11-bit plus sign output value in left-justified two’s-complement format within a 16-bit word. Across the nominal range, 0, 512 and 1024 scaling units correspond to 1 V, 3 V and 5 V, respectively. With the lowest four bits set to zero, the output words are 0000h, 2000h and 4000h.

The module’s 0–100% conversion time is 0.15 ms maximum. Siemens specifies an operating error limit of ±0.6% over 0–60 °C.

Field supply and two- or four-wire connections

Field wiring lands on the S5 bus unit terminals. If the existing unit is a 6ES5 700-8MA11 or 6ES5 700-8MA22, record terminal numbers and jumpers before removal. The field supply connects to terminal 1 (L+) and terminal 2 (M). The permitted supply range is 20–30 V DC, including ripple.

Channel 0 uses terminals 4 (QV), 6 (MANA), 3 (S+) and 5 (S−). Channel 1 uses 8 (QV), 10 (MANA), 7 (S+) and 9 (S−). QV is the voltage output, MANA is the analog return, and S+ and S− are the voltage sense terminals.

With four-wire wiring, run S+ and S− to the receiving device’s input terminals. The module senses the voltage at the load and can compensate for a drop of up to 3 V per line. For two-wire wiring, if line resistance is negligible relative to load resistance, jumper S+ to QV and S− to MANA at the module. Leave unused outputs open. Siemens specifies a maximum shielded cable length of 200 m.

Local PLC and distributed I/O addressing

In a local S5-100U installation, for example with a CPU 102 or CPU 103, install the analog module in slot 0 through 7. Each channel uses one output word. In slot 0, the word addresses are 64 for channel 0 and 66 for channel 1.

In an ET 100U installation connected through an IM 316, the module designation is 2AQ. For ET 200U, check the station interface and DP configuration. The module uses four output bytes. Siemens lists the numeric identifiers as 021 for DP Siemens and 097 for DP Standard.

Editor’s note

Check the label. When selecting a spare, read the complete 6ES5 470-8MD12 order number, including the last two digits. The 8MD11 also carries the 2 × 1–5 V front marking.

Record the addresses. Before replacement, note the slot and the program’s output word for each channel. At a distributed station, also record the module identifier and start address.

Check the field supply. If both channels fail to respond, one of the first checks is the voltage across terminals 1 and 2. Verify the 24 V DC field supply at these terminals.

Measure at the load. During a controlled test, check the 1 V, 3 V and 5 V commands at the receiving device. If the voltage is correct at the module and low at the load, check line drop, the S+/S− wiring and the receiving device’s input resistance.

Trace the command and feedback separately. If valve position is returned through a separate analog input, such as a 6ES5 464-8ME11 4–20 mA input module, measure the 1–5 V command first, then check the feedback current.

OtomasyonAVM resources and PDFs

Siemens SIMATIC S5 systems and module overview

OtomasyonAVM SIMATIC S5 PDF archive page

Siemens ET 200 distributed I/O manuals and PDF archive

Related topics

Related versions include the 6ES5 470-8MD11 two-channel 1–5 V output, the 6ES5 470-8MA12 ±10 V output and the 6ES5 470-8MC12 4–20 mA output.

Category navigation

SIMATIC S5 90/110 module family · SIMATIC S5 analog modules

Siemens external references

SIMATIC S5-100U system manual — 6ES5 470-8MD12 technical specifications

SIMATIC S5-90U/S5-95U system manual — four-wire connection and output values

SIMATIC ET 100U distributed I/O manual — module specifications and wiring

SIMATIC ET 200U station manual — DP module identifiers and address space