6ES5 095-8MA01

Siemens 6ES5 095-8MA01 | SIMATIC S5-95U Compact PLC

The 6ES5 095-8MA01 is a 24 V DC S5-95U basic unit in the Siemens SIMATIC S5 range. It has 16 × 24 V DC digital inputs, 16 × 24 V DC digital outputs, 8 analog inputs and 1 analog output. The Siemens data sheet also lists 4 alarm inputs, 2 counter inputs and 1 PG interface.

Front connector and 24 V DC supply

The 40-pin front connector carries 24 V DC field signals from devices such as inductive sensors and control pushbuttons. The Siemens S5-95U drawing shows digital inputs at I32.0–I33.7 and digital outputs at Q32.0–Q33.7. The German manual uses E for inputs and A for outputs.

The CPU supply and the digital output load supply have separate connections. Check the existing 24 V DC power supply and output supply groups against the panel wiring diagram. Siemens also lists the PS 931 power supply as an S5-95U accessory.

The Siemens accessory list identifies the 6ES5 490-8MA12 as a 40-pin front connector with crimp contacts. Check the connector type, contacts and wire labels when transferring the existing I/O wiring.

Analog I/O, alarm and counter inputs

The S5-95U family manual shows a 0–10 V range for the analog inputs. The single analog output provides 0–10 V or 0–20 mA, depending on the connection. QV and QI are the voltage and current terminals for the same output channel. The alarm inputs handle event signals, and the two counter inputs handle pulse counting.

STEP 5, PG connection and memory

The unit has one PG interface for PLC programming and monitoring with STEP 5. For a PG 7xx programmer, the 6ES5 734-2BD20 is one cable option. Check the programmer model and TTY interface when selecting an S5 programming cable.

Before replacing the unit, save the STEP 5 backup and the DB1 configuration. Record the order number and capacity of the fitted EPROM or EEPROM memory module. If the cabinet uses S5 expansion modules, record their order and addresses as well.

Hardware revisions and checks for a used unit

Siemens lists the addition of the integrated clock at 8MA01 A02 and the DB1 PMC parameter at A04 to check the 8 KB instruction limit. The 6ES5 095-8MA02 A01 revised the digital I/O power arrangement and reduced the housing depth from 149 mm to 140 mm. The 6ES5 095-8MA03 A01 allowed its 16 KB of memory to be allocated freely between instructions and data blocks.

When considering a 6ES5 095-8MA04 or 6ES5 095-8MA05 replacement, compare the order number, hardware revision and memory module with the existing project. For a used unit, ask for a nameplate photo showing the revision, a PG connection test and test results for the digital, analog, alarm and counter channels. Check CPU and field power separately during PLC diagnostics.

Editor’s Note
Check the existing panel diagram for the 8MA01 CPU and onboard digital I/O power-up sequence. Siemens lists 8MA02 A01 as the revision that allowed the two supplies to be switched on in either order.

Manuals and PDF files

The English Siemens data sheet identifies the exact 6ES5 095-8MA01 and its channel counts. The main hardware section of the German S5-95U manual covers the 8MA03. Page H-1 documents the 8MA01 revisions and the changes introduced with 8MA02. OtomasyonAVM SIMATIC S5 PDF archive