6ES5 470-8MB12
Siemens 6ES5 470-8MB12 SIMATIC S5 2 × ±20 mA Isolated Analog Output Module
The Siemens 6ES5 470-8MB12 is a two-channel, galvanically isolated analog current output module for SIMATIC S5. Each channel delivers a rated −20 mA to +20 mA into a load of up to 300 Ω. The rated field supply is 24 V DC. Siemens lists this order number for the S5-90U, S5-95U, S5-100U, ET 100U and ET 200U.
The module converts PLC commands to bipolar current. On a drive with a ±20 mA reference input, for example, the sign can select the direction and the magnitude can set the reference level. A zero command produces 0 mA. The 470-8MC12 delivers 4 mA at the low end of its rated range.
Which local and distributed I/O configurations use it?
The module plugs into the local I/O bus on the S5-90U, S5-95U and S5-100U with controllers such as the CPU 100 or CPU 103. Check the analog output base address against the station layout and STEP 5 project. The OtomasyonAVM PDF page lists the S5-100U manual.
On distributed I/O, the module is identified as 2AQ with an ET 100U IM 318 CC. For ET 200U, check the configuration supported by the IM 318-B 318-8MB11 or IM 318-B 318-8MB12 interface. The ET 200U manual lists the 470-8MB12 as 2AQ with a four-byte address space. Its numeric identifier is 021 for DP Siemens and 097 for DP Standard.
How are the supply and current outputs wired?
Connect the field supply to terminal 1 (L+) and terminal 2 (M). For two-wire loads, use 4 (+QI) and 6 (MANA) for CH0, and 8 (+QI) and 10 (MANA) for CH1. The outputs are galvanically isolated from one another and from the central grounding point. Return each load to its own channel’s MANA terminal.
Field wiring terminates at the bus unit. This family includes the 700-8MA11 screw-terminal base, 700-8MA21 crimp base and 700-8MA22 enhanced-EMC crimp base. Check the bus unit’s complete order number and coding position. The receiving input and cable together must stay within 300 Ω per channel.
How is the ±20 mA range scaled in STEP 5?
Each channel uses one output word. The module interprets a left-justified two’s-complement value with 11 bits plus sign. In the S5-100U table, −1024, 0 and +1024 scaled units correspond to −20, 0 and +20 mA. With the four low bits set to zero, the corresponding words are KH C000, KH 0000 and KH 4000.
The 8MB12 has a maximum 0-to-100% conversion time of 0.15 ms. The ET 200U table gives 0.10 ms for the 470-8MB11, which has the same ±20 mA range. PLC scan time and distributed I/O communications add to the total response time.
How do the other 470 signal ranges compare?
The 470-8MC11 and 470-8MC12 provide 4–20 mA outputs. The 470-8MA11 and 470-8MA12 provide ±10 V. The 470-8MD11 and 470-8MD12 provide 1–5 V. When selecting a spare from the S5 90/110 module range, match the receiving device’s signal type, rated range and program scaling.
Editor’s note
Look for MB12 on the label. The MC12 also has two current outputs. The difference in current at a zero command matters on machines that use a zero-current reference.
Record the existing installation. Before removing the module, note its slot, bus unit, channel terminals and both output words in the project.
Check common points when both channels fail. Start with the 24 V DC supply at terminals 1 and 2 and confirm that the program writes to the expected output address.
Trace the current path when one channel is off. Check that channel’s QI–MANA terminals, cable continuity and total load resistance.
Verify polarity after replacement. With the field load disconnected, use a suitable test load to measure both channels at zero and at small positive and negative commands.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog input and output modules · S5-100U CPU 100 product page
OtomasyonAVM PDF page listing the S5-100U system manual
Related topics
470-8MB11 ±20 mA analog output · 470-8MC12 4–20 mA analog output · 700-8MA11 screw-terminal bus unit
Browse SIMATIC S5
Siemens SIMATIC S5 · S5 90/110 modules · S5 analog modules
Siemens and other external references
Siemens 6ES5 470-8MB12 data sheet (English PDF)
Siemens S5-100U system manual, analog output scaling table (English PDF)
Siemens ET 200U manual, 470-8MB12 wiring and technical data (English PDF)