6ES5 103-8MA02
Siemens 6ES5 103-8MA02 SIMATIC S5-100U CPU 103, 24 V DC, 10,240-statement RAM
The Siemens 6ES5 103-8MA02 is the CPU 103 central processing unit for the S5-100U in the SIMATIC S5 range. It runs from 24 V DC and has internal RAM rated for 10,240 STEP 5 statements. It executes the control program and exchanges data with the I/O modules over a serial bus. This version supports an integral real-time clock, OB2 process interrupts and OB13 time-controlled program processing.
The CPU reads input states and updates the outputs according to the STEP 5 program. The CPU 100 and CPU 102 are separate processor types in the same family. Within the CPU 103 range, check whether the unit is an 8MA01, 8MA02 or 8MA03. Siemens documents the integral clock from 8MA02 and clock parameter assignment through DB1 from 8MA03.
Power supply and the S5-100U bus
The CPU accepts 18–34 V DC, with a nominal input of 24 V DC. Its internal supply provides 9 V to the peripheral modules. The DIN rail-mounted S5 bus units connect to the CPU and to one another through ribbon cables. The 6ES5 700-8MA11 uses screw terminals. The 6ES5 700-8MA22 uses snap-in crimp connections.
I/O capacity and slot addressing
The CPU 103 supports up to 256 digital and 32 analogue I/O channels, each figure counting inputs and outputs together. Examples include the 6ES5 430-8MB11 digital input module and the 6ES5 441-8MA11 digital output module. Siemens specifies 16 inputs and 16 outputs for the combined 6ES5 482-8MA13 and assigns it to slots 0 through 7.
Analogue modules also use slots 0 through 7. The 6ES5 466-8MC11, for example, has four 0–10 V inputs. If an analogue module moves to a different slot, check the peripheral addresses in the STEP 5 program against the new layout.
OB2, OB13 and the real-time clock
OB2 handles process interrupts from the field. OB13 runs time-controlled program sections. In an installation that uses hardware interrupts, record the position and alarm wiring of interrupt-capable bus units such as the 6ES5 700-8MB11 and 6ES5 700-8MB21. For the 8MA02, the manual describes configuring the clock through system data and the user program.
Internal RAM, memory submodule and backup battery
Check the CPU’s 10,240-statement RAM and the capacity of the plug-in 375 memory submodule separately. The 6ES5 375-0LC31 EEPROM, for example, holds 4,096 statements. Siemens lists the 6ES5 980-0MB11 3.4 V, 850 mAh lithium backup battery for S5-100U CPUs.
Editor’s note
Record the complete order number. Read the 8MA02 suffix on the label and check whether the STEP 5 project uses the clock, OB2 or OB13 before selecting a spare.
Back up the running program before using COPY. Use the programmer to save a separate copy of the program and data blocks from the CPU. Compare the contents of the fitted EPROM or EEPROM with the blocks in the running controller.
Collect the diagnostics before clearing a STOP fault. Note the RUN, STOP and battery indicators before an overall reset. If the CPU is reachable through the correct programmer cable, read the ISTACK in STEP 5.
Plan a shutdown around a battery warning. Verify the program backup first. On machines that use the clock, check the date, time and any operating-hours counter after the replacement.
Test the spare with the installed I/O layout. Confirm the transition to RUN, programmer access and communication with the I/O modules. If the project uses process interrupts, verify under controlled test conditions that the relevant input calls OB2.
OtomasyonAVM resources and PDF archive
About Siemens SIMATIC S5 PLCs · OtomasyonAVM S5 manuals and PDF archive
Related topics
CPU 103 8MA01 · CPU 103 8MA03 · 700-8MB11 interrupt bus unit
Browse this family
Siemens S5 PLCs → SIMATIC S5 → S5 bus units
External references
Siemens S5-100U Closed-Loop Control — ordering entry for 6ES5 103-8MA02
Siemens S5-100U manual — CPU 103 technical specifications (Russian)
Siemens S5-100U System Manual — OB13 and interrupt process images
Siemens S5-100U System Manual — 8MA02 real-time clock and version differences