6ES5 470-8MA12
Siemens 6ES5 470-8MA12 – SIMATIC S5 470 Two-Channel ±10 V Analog Output Module
The Siemens 6ES5 470-8MA12 is an isolated SIMATIC S5 analog output module with two voltage channels, each rated for −10 V to +10 V. Siemens lists it for the S5-90U, S5-95U, S5-100U, ET 100U and ET 200U. It takes a 24 V DC field supply and requires a minimum receiving input resistance of 3.3 kΩ. The specified conversion time from 0% to 100% is 0.15 ms maximum.
The module turns a numeric PLC command into an analog voltage for a field device. With a drive or servo amplifier configured for a ±10 V command, polarity can select direction while the voltage magnitude sets the command level. The receiving device's input settings and the machine design determine what each polarity means. This signal path illustrates the difference between an analog input and an analog output.
24 V supply and terminal assignment
The field supply connects to terminal 1 (L+) and terminal 2 (M). Siemens specifies a 20–30 V DC supply range including ripple. The S5-100U manual gives typical current draws of 100 mA from L+ and 120 mA from the CPU's 9 V rail, with typical module power dissipation of 3.1 W. Check the installed S5 power supply and identify whether the installation uses a screw-terminal bus unit or a crimp-terminal bus unit.
Channel 0 uses terminal 3 for S+, 4 for QV, 5 for S− and 6 for MANA. Channel 1 uses the same sequence on terminals 7, 8, 9 and 10. QV is the voltage output and MANA is the channel's analog return. The outputs are galvanically isolated from each other and from the central ground point. Follow each channel's own return in the panel wiring diagram when reconnecting the terminal block.
Two-wire and four-wire voltage connections
With four-wire wiring, QV and MANA carry the output to the load. Separate S+ and S− sense leads connect directly across the load. The module regulates voltage at that point and can compensate for drops of up to 3 V per lead under the manual's specified conditions.
Siemens allows two-wire wiring when lead resistance is negligible compared with the load resistance. At the module, link S+ to QV and S− to MANA on the channel in use, then connect the load between QV and MANA. The S5-100U manual specifies leaving unused outputs open. It lists 200 m as the maximum shielded cable length. The S5-90U/S5-95U manual also specifies a capacitive load of less than 100 nF, including the cable. When checking the existing S5 cabling, account for both cable capacitance and receiving input resistance.
STEP 5 scaling and channel addresses
The module represents the output with 11 bits plus sign. The nominal endpoints are −1024 for −10 V and +1024 for +10 V. A scaled value of 0 gives 0 V, while −512 gives −5 V and +512 gives +5 V. If the PLC program writes the output word directly, the signed value is left-aligned in two's complement format. With the bottom four bits set to zero, example words are C000h for −10 V, 0000h for 0 V and 4000h for +10 V.
On a local S5-100U CPU station, each analog channel uses one output word. For example, a module in slot 0 uses bytes 64–65 for channel 0 and bytes 66–67 for channel 1. For a distributed station, use its configured address map. The ET 100U IM 318 interface and the ET 200U PROFIBUS-DP interface serve different station layouts.
Editor’s note
Record the full order number and the 2 × ±10 V marking on the module you remove. The similar-looking 6ES5 470-8MA11 also provides ±10 V outputs. Match the replacement's full order number to the installed CPU, station and wiring arrangement.
If a channel stops responding, check the 24 V supply, output word and QV-to-MANA voltage separately. When the command changes but the terminal voltage stays fixed, confirm the channel address first. During PLC troubleshooting, also check whether another part of the program writes to the same word.
If a replacement gives a low or unstable voltage, trace S+ and S− back through the wiring. Two-wire installations use local links, while four-wire installations take the sense leads all the way to the load. A photo of the original terminals helps distinguish the two arrangements before reconnecting the module.
When the module voltage is correct but the receiving device reads a different value, compare both ends with the load connected. This helps isolate lead voltage drop, a loose terminal or a low receiving input resistance. If only one channel is affected, trace that channel's analog return first.
For a bench check, use a suitable test load in a setup disconnected from the machine. Apply negative, zero and positive commands to both channels. Readings at −5 V, 0 V and +5 V help confirm that each channel follows the command in both polarities.
OtomasyonAVM S5 pages and PDF manuals
The S5 PDF files page lists the S5-100U system manual. See printed page 11-19 for the wiring diagram, 11-21 for the output value table and 14-56 for this module's specifications. For more on the platform, see the Siemens S5 PLC guide and the S5 90/110 module directory.
Related topics
The full order number identifies the signal type in the 470 family. The 6ES5 470-8MB12 has two ±20 mA outputs, the 6ES5 470-8MC12 has two 4–20 mA outputs, and the 6ES5 470-8MD12 has two 1–5 V outputs. For voltage feedback, the 6ES5 466-8MC11 is an example of an analog input module for 0–10 V signals.
Site navigation
Siemens S5 PLC › SIMATIC S5 › S5 analog modules
External references
Siemens product data sheet covering supported systems and output type. 6ES5470-8MA12 data sheet (PDF)
Siemens S5-100U system manual covering wiring and output scaling. S5-100U system manual (PDF)
Siemens S5-90U/S5-95U system manual covering specifications and capacitive load. S5-90U/S5-95U system manual (PDF)
Siemens ET 100U manual showing four-wire connections and terminal assignments. ET 100U distributed I/O manual (PDF)