6ES5 100-8MA02

Siemens 6ES5 100-8MA02 SIMATIC S5-100U CPU 100

The Siemens 6ES5 100-8MA02 is the CPU 100 central processing unit for the SIMATIC S5-100U. Its nominal input is 24 V DC, with a permissible range of 18–34 V DC. It has internal RAM for 1,024 STEP 5 statements and supports an EPROM or EEPROM memory submodule.

The CPU runs the SIMATIC S5 program, reads the inputs and updates the outputs. Its integrated supply provides 9 V DC at 1 A for the I/O bus and 5.2 V DC at 0.65 A for the programmer interface. If the cabinet contains a PS 930, PS 931 or PS 950, use the machine drawing to trace the 24 V circuits feeding the CPU and the field loads separately.

How do you size the I/O configuration?

The Siemens technical table gives separate upper limits of 256 digital channels and 8 analog channels, in each case counting inputs and outputs together. Include both digital input modules and digital output modules, such as any fitted 421-8MA12 and 441-8MA11, in the calculation.

For a mixed configuration, the bus allows 256 data bits in total, with up to 128 analog data bits within that total. Check the individual bit requirements of the analog modules fitted, for example a 464-8MA11 analog input or 470-8MA11 analog output. Use the combined bit count when assessing a mixed layout.

Bus units and program memory

In an S5 mounting arrangement, the 700-8MA11 is a screw-terminal bus unit. The 700-8MA21 and 700-8MA22 are crimp-terminal versions. Record the slot order and any S5 interface modules during service. Compare the installed module sequence with the machine’s I/O address list.

The CPU 100 runs from internal RAM. A suitable S5 memory submodule can store the program. Siemens lists the 6ES5 980-0MB11 backup battery for this CPU family. Verify the program backup and the condition of the battery that backs up retentive data separately.

Why does the 8MA02 suffix matter?

For the CPU 100, the Siemens IP 267 stepper motor controller manual specifies 6ES5 100-8MA02. Check the nameplate suffix to distinguish it from the similar 6ES5 100-8MA01. If considering a CPU 102 or CPU 103, check the program, I/O capacity and special modules against that CPU’s own documentation.

Editor’s note

Check the 24 V input when the fault occurs. If the CPU restarts, record how the voltage between L+ and M changes when the load comes on.

Recheck the bit count if adding I/O puts the CPU in STOP. Siemens states that the PEU bit is set in the ISTACK when the expansion limit is exceeded.

Match the full order number when choosing a spare. Photograph the original CPU label. If an IP 267 is fitted, record the 8MA02 suffix on the service ticket.

Verify the program backup before removal. Record the EPROM or EEPROM label, the program version in the CPU and the machine data needed for restoration.

Mark the cables and slots before dismantling. After safe isolation, compare the S5 cables and connectors, bus connections and field supplies with the machine drawing.

OtomasyonAVM resources and PDFs

About Siemens S5 PLCs · S5 90/110 modules · Siemens S5 PDF archive. The exact CPU 100 specifications are on printed page 14-7 of the Siemens manual linked below.

Related topics

CPU 100 8MA01 · CPU 102 8MA02 · CPU 103 8MA02 · IP 267 stepper motor controller

S5 navigation

Siemens S5 PLCs · SIMATIC S5 CPUs · S5 90/110 modules · S5 power supplies

Siemens and other external references

Siemens SIMATIC S5-100U system manual, page 14-7 (CPU 100 specifications for 6ES5 100-8MA02)

Siemens IP 267 stepper motor controller manual (CPU 100 8MA02 compatibility requirement)

Siemens 6ES5100-8MA02 ordering data sheet (Exact order number and 24 V / 9 V supply information)