6ES5 464-8MA11
Siemens 6ES5 464-8MA11 — 4-Channel ±50 mV Analog Input Module
6ES5 464-8MA11 is a 464-series measurement module with four ±50 mV analog inputs for Siemens SIMATIC S5 systems. Its applications include S5-90U, S5-95U, S5-100U, ET 100U and ET 200U installations. Within the S5 analog module range, this version provides 12 bits plus sign and an input resistance of 10 MΩ for low-level voltage measurement.
The module can acquire the millivolt signal produced by a thermocouple. In a machine using type J or type K thermocouples, temperature measurement depends on the sensor characteristic, wiring polarity and reference-junction temperature. The voltage acquired by the MA11 is not automatically a temperature reading in °C.
Input range and temperature conversion
The nominal input range is −50 to +50 mV. The selectable linearization and temperature-compensation functions of the 6ES5 464-8MA21 must not be assumed to exist on the MA11. Before choosing a replacement, check how the existing program converts millivolts to temperature and how external compensation is arranged.
Identify the thermocouple type and applicable thermocouple standard. Cable colour alone is insufficient identification: the sensor label, extension wiring and program must agree on the characteristic being measured. An external compensation box must also match the thermocouple type.
Terminals, compensation and isolation
The input pairs are channel 0: 3 (+) / 4 (−), channel 1: 5 (+) / 6 (−), channel 2: 7 (+) / 8 (−), and channel 3: 9 (+) / 10 (−). See the 6ES5 700-8MA11 bus unit and S5 cables and connectors when checking the connection hardware. Confirm the terminal numbers against the module label and machine wiring.
Terminals 1 (+) and 2 (−) are for the compensation box. Siemens specifies a jumper between these terminals when no compensation box is used. An external box requires an isolated supply. The module itself is powered from the +9 V I/O bus; terminals 1 and 2 are not a 24 V power input.
The input group is galvanically isolated from ground; the channels are not isolated from each other. Check common-mode limits and grounding arrangements before connecting sensors at different potentials. The specified maximum length for shielded signal cable is 50 m; routing and electrical noise still require attention.
Channel selection, timing and raw values
Front switches select one, two or four channels, 50/60 Hz interference suppression and wire-break indication. The enabled channel count must agree with the address allocation for the S5 I/O modules. Integration takes 20 ms at 50 Hz or approximately 16.6 ms at 60 Hz. At nominal full scale, maximum encoding time per channel is 60 ms or 50 ms, respectively.
In the PLC program, nominal inputs of −50 / 0 / +50 mV correspond to −2048 / 0 / +2048 measurement units. The data uses left-justified two’s complement. With the lower three bits clear, the corresponding input words are C000h / 0000h / 4000h. Evaluate the low-byte E wire-break and OV overflow bits separately from the measured value.
Differences between similar order codes
The 6ES5 464-8MB11 measures ±1 V, the 6ES5 464-8MC11 measures ±10 V, the 6ES5 464-8MD11 measures ±20 mA, and the 6ES5 464-8ME11 measures 4–20 mA. Similar housings do not make these modules direct replacements for the MA11.
The 6ES5 464-8MF11 is a two-channel Pt100 / ±500 mV version. The difference between a Pt100 and a thermocouple affects the required input hardware: match both the sensor type and signal range.
Editor’s note
Start with the basics: is the correct millivolt signal reaching the input? An incorrect temperature display does not, by itself, prove that the card has failed. When troubleshooting the PLC, work through the sensor, wiring, compensation and conversion logic one step at a time. It can save an unnecessary replacement.
When buying a used module, look beyond “464” and confirm the full 8MA11 suffix. Photograph the original label, switch settings and terminal connections before removal. A few clear pictures are often more useful than trying to remember the setup once the replacement is in your hand.
For a bench check, use a suitable millivolt calibrator and test zero, positive and negative points. Check every channel you intend to use. One good reading on one channel is a useful start; it is not a complete test of the card.
If a digital meter shows fluctuations at the sensor terminals, allow for the module’s wire-break test pulses before blaming electrical noise. Disabling the indication does not switch off the test current. Understand that behaviour first, then investigate the wiring with a measurement method suited to the signal.
Heating the probe and seeing a changing value is only the beginning. Check the reference junction, polarity and agreement with a known temperature as well. A dependable SIMATIC S5 measurement relies on the whole signal chain working correctly, so give those final checks the time they deserve.
OtomasyonAVM resources and PDFs
+ Browse the S5 analog modules and Siemens S5 PLC pages for related equipment.
+ OtomasyonAVM S5 PDF archive and system manuals. For this module, read the S5-100U analog value processing chapter together with the exact 464-8MA11 technical pages. The Siemens manuals linked below are in English.
Related topics
+ 6ES5 464-8MA21: ±50 mV version with linearization · 6ES5 464-8MF11: Pt100 / ±500 mV · Pt100 versus thermocouple.
Browse SIMATIC S5
+ S5 analog modules · S5 90/110 I/O modules · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand equipment.
Siemens and external references
+ Siemens S5-90U/S5-95U System Manual — English; pp. 15-38–15-39, exact 464-8MA11 order code.
+ Siemens ET 100U Manual — English; pp. 3-56–3-57 thermocouple and compensation wiring.
+ Siemens ET 200U Manual — English; p. 7-4 wiring diagrams and pp. 8-41–8-42 module data.