6ES5 464-8MB11

6ES5 464-8MB11 – 4-Channel ±1 V Analog Input Module

Siemens 6ES5 464-8MB11 is a four-channel ±1 V analog input module documented for S5-90U, S5-95U, S5-100U and ET 100U systems. This S5 analog module converts voltage signals into a 12-bit plus sign representation. Its front selector enables one, two or four channels to pass low-level voltage measurements to the Siemens S5 PLC.

The module reads the −1 V to +1 V output of a suitable measuring transducer. The analog signal can then be scaled to an engineering value in the program. In analog measurement applications, check the actual transducer range first: ±10 V and 4–20 mA signals do not directly match this input range.

Accuracy and measurement updates

Input resistance is 10 MΩ. The specified basic error limit is ±0.1%, with an operational error limit of ±0.35% over 0–60 °C. The input group is galvanically isolated from the grounding point; individual channels are not isolated from each other. This matters when selecting S5 peripheral modules for sources operating at different potentials.

Integration time is 20 ms at 50 Hz or approximately 16.6 ms at 60 Hz. At the nominal value of 2048 units, maximum encoding time per input is 60 ms / 50 ms, respectively. Selecting fewer channels improves update time. Treat the PLC scan time and the analog module’s measurement update time as separate quantities.

Power supply and two-wire connections

The module uses the internal +9 V peripheral bus supply of the SIMATIC S5 system; it does not require an external L+ field supply. Check the S5 power supply and bus connections together. Do not apply a 24 V supply to the measurement inputs.

Two-wire voltage connections use channel 0: 3 (+), 4 (−); channel 1: 5 (+), 6 (−); channel 2: 7 (+), 8 (−); channel 3: 9 (+), 10 (−). Maintain polarity when arranging cables and connectors, and follow the system manual for grounding and shielding. Siemens specifies a maximum shielded cable length of 200 m.

Operating mode, scaling and diagnostics

The front operating mode selector sets the line-frequency rejection, active channel count and wire-break indication. One-channel operation uses Ch.0; two-channel operation uses Ch.0 and Ch.1; four-channel operation uses Ch.0–Ch.3. Match the selected channels to those read by the PLC program.

The nominal scale is −1 V = −2048 units, 0 V = 0, +1 V = +2048 units. Raw data uses left-justified two’s complement; with the status bits clear, the corresponding words are C000h / 0000h / 4000h. The S5-90U/S5-95U manual specifies FB250 with channel type y=6 for normalization. During PLC troubleshooting, check the raw word, sign and status bits together.

When wire-break indication is enabled, a detected fault lights the red LED and sets the channel’s F error bit. Detection uses test-current pulses at the input. Disabling the indication does not stop this test current; the pulses can cause apparent fluctuations on a digital voltmeter.

Distinguishing similar order numbers

6ES5 464-8MC11 accepts ±10 V, 6ES5 464-8MD11 accepts ±20 mA, and 6ES5 464-8ME11 accepts 4–20 mA. 6ES5 466-8MC11 is the 0–10 V input model. Their signal ranges differ; a similar housing does not establish interchangeability.

Editor’s note

Take a moment to read the label before replacing anything: the required code here is 464-8MB11. Even if you know the S5 system well, check those final characters. One letter can change the entire measurement range.

A sensor producing a very small voltage is not automatically a good match. The ±50 mV 464-8MA11 and 464-8MA21 modules serve a different range. Start with the sensor’s nameplate and actual output; trying to correct a range mismatch in software usually costs more time later.

For temperature measurements, identify the sensor type first. Modules such as 464-8MF11 and 464-8MF21 are documented for Pt100 connections; this ±1 V input needs a different signal. Knowing what the sensor delivers makes choosing the right card much easier.

When checking a used module, work through 0 V, +0.5 V and −0.5 V on every enabled channel with a suitable voltage source. Keep the input role separate from that of analog output modules such as the 470-8MA12, and measure the test source before connecting it. If one channel differs, repeat the check with the same cable and source.

Do not condemn the card just because a meter reading moves around. Consider this model’s wire-break test pulses, the source output and the wiring together. Check the channel-count and 50/60 Hz settings as well. A small setup detail should not send a serviceable module to the scrap bin.

OtomasyonAVM resources and PDFs

+ S5 analog modules: input and output cards.

+ About Siemens S5 PLCs: system and maintenance information.

+ S5 PDF archive: system and module manuals. The English Siemens manuals used to verify this model are linked under external references below.

Related topics

+ 464-8MC11: four-channel ±10 V voltage input.

+ 464-8MD11: four-channel ±20 mA current input.

+ 464-8ME11: four-channel 4–20 mA current input.

Browse SIMATIC S5

S5 analog modules · S5 module groups · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page

Siemens and external references

+ Siemens S5-100U System Manual, EWA 4NEB 812 6120-02b, English: pages 14-42–14-43, wiring and specifications.

+ Siemens S5-90U/S5-95U System Manual, EWA 4NEB 812 6115-02b, English: pages 15-58–15-61, settings, diagnostics and scaling.

+ Siemens ET 100U Manual, EWA 4NEB 812 6040-02a, English: pages 2-40–2-41, exact-order-number module data.