6ES5 464-8ME11

Siemens 6ES5 464-8ME11 – 4-Channel 4–20 mA Analog Input Module

The 6ES5 464-8ME11 is a SIMATIC S5 module with four 4–20 mA analog inputs. It supports S5-90U, S5-95U and S5-100U systems. This member of the S5 analog module range offers one, two or four active channels, with a digital representation of 12 bits plus sign.

It reads suitable 4–20 mA outputs from pressure sensors, level sensors and other analog sensors. Both loop-powered two-wire transmitters and separately powered four-wire transmitters are supported, using different wiring arrangements.

Input range and differences from related modules

The nominal input is a 4–20 mA current signal. Understanding 0–10 V versus 4–20 mA and the analog signal type helps identify the correct module. Check the transmitter's output specification before selecting a replacement.

The 6ES5 464-8MD11 accepts ±20 mA, the 6ES5 464-8MC11 accepts ±10 V, and the 6ES5 464-8MB11 accepts ±1 V. These related modules require separate checks of wiring and scaling before any substitution.

For direct Pt100 measurements, consider the 6ES5 464-8MF11 or the 6ES5 464-8MF21 with Pt100 linearization. The 464-8ME11 reads a suitable transmitter's 4–20 mA output rather than measuring Pt100 resistance directly.

Connecting two-wire and four-wire transmitters

For two-wire transmitters, terminal 1 is L+ and terminal 2 is M. The nominal supply is 24 V DC, with a permissible range of 20–30 V DC. Channel terminal pairs are CH0: 3–4, CH1: 5–6, CH2: 7–8 and CH3: 9–10. Record the terminal numbers before disturbing existing S5 wiring and connections.

A four-wire transmitter needs its own supply. In the Siemens wiring diagram, its positive current output connects to the corresponding terminal 4, 6, 8 or 10, while its negative output connects to terminal 2. This differs from the two-wire transmitter connection.

When both transmitter types share a module, follow the mixed connection diagram in the S5-90U/95U manual. That arrangement requires the four-wire transmitters to be galvanically isolated from the module.

Channel selection, measurement time and isolation

The front operating-mode switch selects 50/60 Hz interference suppression and the number of active channels. Compare these settings when replacing S5 I/O modules. Integration time is 20 ms at 50 Hz or 16.6 ms at 60 Hz; this is not the complete refresh time for all channels.

The input group is galvanically isolated from the grounding reference, but the channels are not isolated from one another. Check common references and isolation requirements when connecting transmitters at different potentials.

Digital representation and scaling

In the manual's measurement units, 4 mA = 512, 12 mA = 1536 and 20 mA = 2560. These figures must be distinguished from the directly read 16-bit word, which uses left-justified data. Check the input format expected by the conversion used in your PLC program.

The S5-90U/95U manual describes normalization using FB250 with channel type 3, “absolute value”. In the Basic Functions package, FB30 uses KD = 12 for this module. Select the block for the actual CPU and project. When comparing readings with analog controllers, use matching engineering ranges.

System compatibility and fault finding

The module is also documented for ET 100U and ET 200U distributed I/O. When reviewing S5 CPU options, check the station, bus unit and addressing together. Our Siemens S5 PLC overview provides background on the system structure.

This module has no hardware wire-break indication. During PLC troubleshooting, check loop current, transmitter power and the raw reading first. Software can monitor values below the expected range; a low reading alone does not establish a module fault.

Editor’s note

Give the label a careful look before ordering a replacement. Compare the complete 8ME11 suffix with the original module. Similar housings can be misleading, and a few minutes here can save a long troubleshooting session later.

Establish whether the transmitter is a two-wire or four-wire device before reconnecting it. In an older cabinet, cable colours may tell only part of the story. Terminal numbers and the transmitter's own diagram are better guides.

If the displayed value looks wrong, work through the signal patiently. Apply a known current, check the raw reading, then follow the scaling. A methodical check can spare a perfectly serviceable module from unnecessary replacement.

Take a photograph of the original channel and 50/60 Hz settings before removing the module. It is a small habit that gives you a reliable starting point after the change.

For a used module, ask for more than a power-on check. Have the channels you need tested at 4, 12 and 20 mA, and request the results. A trial with your own transmitter is useful when practical.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLC and S5 analog modules: system information and related modules.

+ Siemens S5 PDF archive: access to S5-100U and related system manuals. The manufacturer manuals below contain English instructions.

Related topics

+ 464-8MD11: ±20 mA input · 464-8MC11: ±10 V input · 464-8MF11: Pt100/±500 mV input.

+ 0–10 V and 4–20 mA signals · PLC measurement checks and troubleshooting.

Browse SIMATIC S5

S5 analog modules · S5 module groups · SIMATIC S5 CPUs · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens S5-100U System Manual – English, wiring 11-4–11-5; specifications 14-48–14-49.

+ Siemens S5-90U/95U System Manual – English, 15-72–15-77; mixed wiring and scaling.

+ Siemens ET 100U Manual – English, module specifications and analog processing.

+ Siemens ET 200U Manual – English, 7-7–7-8 and 8-51–8-52.

+ Siemens Basic Functions supplement – multilingual, English FB30 and KD = 12 instructions.