Delta Servo I/O Connections

Delta Servo I/O Connections

Delta servo CN1 I/O connections carry control and status signals between a PLC or motion controller and the servo drive. The drive reads the assigned inputs and controls the servo motor according to its model and operating mode. Assigned outputs report ready, alarm and in-position status to the machine controller.

Match the CN1 accessory to the full drive code

ASD-CNSC0050 is the 50-pin CN1 connector listed in the ASDA-A2 catalogue. ASD-BM-50A is the terminal block module that brings CN1 signals out to cabinet terminals. When buying a used terminal block, check whether the connecting cable is included.

ASD-IF-SC5020 is a spring-terminal CN1 quick connector for ASDA-A2 and ASDA-A2R. Its manual lists 5 DI, 4 DO, pulse command inputs and an open-collector Z output. Check the J1 and J2 tables for each signal your application requires.

ASD-CNSC0026 is the 26-pin CN1 connector listed in the ASDA-A2-E catalogue and the ASDA-A3 manual for A3-E/F models. Before moving a cable between drives, compare the pin and signal tables for both models. Use the dedicated CN1 drawing for A3-L/M.

ASDBCNDS0025 is the 25-pin CN1 connector for the legacy ASDA-B series. When replacing the drive with an ASDA-B2, compare the replacement's CN1 table with the termination schedule of the existing cabinet cable.

CN1 inputs, outputs and command signals

DI — Signals sent to the drive. SON enables the servo and ARST resets alarms. The physical DI number and active logic for home and travel limit signals depend on the drive setup. When connecting a PLC transistor output, check PNP/NPN and sink/source compatibility, the input common and the supply against the model-specific drawing.

DO — Status signals from the drive. SRDY reports drive ready, ALRM reports alarm status, TPOS reports in-position status and ZSPD reports zero speed. If BRKR is assigned, follow the model's brake control drawing. Output type, polarity and current rating determine which PLC input or interposing relay can be used.

Motion commands. In pulse-train position control, match the pulse format and the differential or open-collector interface. For analog speed and torque control, check the active drive mode. On installations using EtherCAT, CANopen or Modbus RS-485, identify the command source and the field signals handled by CN1 for the exact model.

CN2 — Motor feedback. The motor encoder connects to the drive at CN2. Where available, CN1 A/B/Z outputs provide separate signals to the upper-level controller. When replacing a motor, verify the feedback interface, incremental or absolute encoder compatibility and both cable ends.

ASDA-B2 parameter example. DI1–DI8 use P2-10…P2-17 and DI9 uses P2-36. DO1–DO5 use P2-18…P2-22 and DO6 uses P2-37. Record CN1 pin → DI/DO number → parameter → PLC address for each point on the cabinet drawing.

Editor’s Note

Ask for both sides of a used connector. Request photos of the full drive nameplate, the mating face, the wire side and any terminal board. Look for missing locking screws, recessed pins and splices from previous repairs.

Record the cable terminations before removal. Note the wire colours on the cabinet drawing. After isolating power and observing the manufacturer's discharge requirements, disconnect both ends of the cable and check continuity and shorts between adjacent pins. Confirm whether the drawing shows the mating face or the wiring side.

When the PLC output is on and the drive DI stays off, start with the DI common, supply and polarity. If the input changes in the drive monitor, review the function assignment, active control mode and limits in the drive configuration.

Record the alarm code first. Compare the PLC's ALRM bit with the drive display or alarm history. If the axis moves and the machine sequence stalls, review the TPOS assignment, position-error window and positioning tolerance. If the signal drops only during movement, check for cable damage, shield faults and electrical noise.

Back up the settings before a cabinet change. Keep the DI/DO map, command source and limit status with the service record. Follow the drive-specific safety drawing for STO wiring. The record gives the next servo maintenance technician a baseline for checking the cable and drive settings.

CN1 wiring manuals and catalogues

ASDA-A2 user manual · EN, 781 pages. Section 3.4 covers CN1, 3.4.5 the quick connector and 3.14.4 the applicable 26-pin variants.
ASDA-A2 accessory catalogue · EN, 72 pages. ASD-CNSC0050 and ASD-BM-50A dimensions. See PDF page 61 for ASD-IF-SC5020.
ASDA-A2-E catalogue · EN, 8 pages. ASD-CNSC0026 accessory listing.

ASDA-B2 user manual · EN, 351 pages. Section 3.3 covers CN1, 3.3.4 covers DI/DO assignments and Chapter 10 covers alarms. B2 2010 archive edition.
ASDA-A3 user manual · EN, 1,287 pages. Section 3.4.1 covers A3-L/M, 3.4.2 covers A3-E/F and Appendix B.8 lists CN1 accessories.
ASDA-B user manual · EN, 321 pages. Legacy 25-pin CN1 in section 3.3 and ASDBCNDS0025 in the appendix.

Related topics

Industrial servo applications · Multi-axis synchronization · Dynamic servo performance

Delta Servo Cables · Power Connectors · Communication Units · Motion Control Cards · Absolute Encoder Peripheral Units

Delta Servo Modules and Accessories · Delta Servo Manuals · Second-Hand Delta Equipment

External references · A2 manual · A2-E catalogue · B2 manual · A3 manual · B manual