Delta DVP08SN11T
Delta DVP08SN11T — 8 NPN transistor output module
The Delta DVP08SN11T is a Slim expansion module for compatible DVP PLC series. It has 0 inputs and 8 NPN sinking transistor outputs, with one shared C0 terminal. Typical loads include 24 V DC indicator lamps, PLC-compatible interface relays and small DC valves within the output ratings.
An inductive sensor for part detection, a photoelectric sensor for detecting products as they pass or a limit switch for end-of-travel feedback connects to the PLC input side. The CPU processes those signals and drives the load through a Y output on the DVP08SN11T. See PLC input and output modules for the signal path and NPN and PNP for current direction.
Wiring and current limits
The terminals are marked C0 and Y0–Y7. Connect C0 to the load supply 0 V and each load between supply +V and its Y terminal. When the output turns on, it sinks load current to 0 V through C0. The PLC expansion connector powers the module electronics. Use a suitable 5–30 V DC supply for field loads.
Section 7.5.7 of the Delta module manual specifies 0.30 A per output and 1.2 A at C0. The series overview lists 2 A per common. Use the model-specific wiring diagram’s 1.2 A total for load sizing. Apply the channel limit at the temperature inside the cabinet. The ratings are 0.30 A at 40 °C, 0.20 A at 45 °C, 0.15 A at 50 °C and 0.10 A at 55 °C.
Eight loads drawing 120 mA each total 0.96 A at C0. At 55 °C, however, each channel exceeds the 100 mA limit. Follow the manufacturer’s surge suppression guidance for DC relay and valve coils. Check polarity where a diode is used for suppression and select a fuse suited to the load circuit.
Software, programming cable and addressing
PLC programming and the cable connection are handled by the host CPU. For families such as DVP-SS2, DVP-SA2 and DVP-SX2, check the exact CPU model for expansion compatibility, port type and module limits. Use WPLSoft or ISPSoft according to CPU support. Set up ISPSoft communications in COMMGR. For compatible 8-pin RS-232 programming ports, see the UC-PRG020-12A and other DVP programming cables.
Y0–Y7 are the terminal markings. Actual ladder addresses depend on the CPU and expansion order. If the first assigned output is Y20, the module uses Y20–Y27. Check the machine’s I/O map before commissioning.
Editor’s Note
When buying used, read the full label. The T suffix identifies NPN sinking outputs. The TS suffix identifies PNP sourcing outputs.
Check C0 for looseness, darkening or melted plastic. A single faulty common connection can affect all eight channels.
Use a fused, current-limited 24 V DC supply and a small DC test load. Exercise Y0 through Y7 individually.
If the output LED turns on and the load stays idle, use a multimeter to check the C0 return and the load’s +V supply with the load connected.
If the ladder monitor shows an active output and the module LED stays off, check the Y address and module order. Switch off power before inspecting the expansion connector.
Related topics and modules
DVP08SN11TS 8 PNP outputs · DVP08SN11R 8 relay outputs · DVP16SN11T 16 NPN outputs · DVP08SM11N 8 digital inputs · DVP08SP11T 4 inputs and 4 NPN outputs · DVP16SP11T 8 inputs and 8 NPN outputs
Delta main page · Used Delta PLCs · DVP Slim digital modules · DVP expansion modules
PDF files and manuals
External references · DVP Module Manual, section 7.5.7 (EN) · DVP Slim digital I/O instruction sheet (EN)