Delta DVP16SN11T

Delta DVP16SN11T – 16 NPN Transistor Output Expansion Module

Delta DVP16SN11T is a right-side expansion module that adds 16 NPN sinking transistor outputs to compatible Delta DVP Slim PLCs. Its point count is 0 inputs and 16 outputs. The two output groups are labeled Y0–Y7 and Y10–Y17. For other options, see DVP Slim digital modules.

Power supply and UP/ZP terminals

The CPU supplies the module electronics. For the output circuit, wire +24 V from an external 24 V DC supply to UP and 0 V to ZP0 and ZP1. Delta specifies a −15% to +20% supply tolerance and consumption of up to 30 mA for this circuit. Add the load current separately. ZP0 is the return for Y0–Y7 and ZP1 is the return for Y10–Y17.

In a 24 V DC circuit, wire one side of the load to +24 V and the other to its Y output. When the output turns on, it sinks current to 0 V through ZP. Verify sink/source compatibility at the receiving device. NPN and PNP outputs use different current paths and common terminal arrangements.

Output limits and cabinet temperature

Delta's model wiring diagram specifies 5–30 V DC loads and resistive-load limits of 0.3 A per output and 1.2 A per common. Delta's temperature table reduces the per-output limit to 0.30 A at 40 °C, 0.20 A at 45 °C, 0.15 A at 50 °C and 0.10 A at 55 °C. Check both the channel rating at the cabinet temperature and the total common current. Eight 160 mA loads active on one group draw 1.28 A and exceed its limit.

Panel wiring and load selection

The outputs can switch suitable small DC loads or drive an interposing relay coil. When choosing a contactor or valve coil, check inrush and suppression as well as nominal current. A suitable flyback diode or the coil maker's recommended suppressor limits the voltage spike when a DC coil turns off.

In the same panel, an inductive sensor or a limit switch can feed a CPU input while the expansion module switches the load. If an output LED lights and its load stays off, check the corresponding ZP return and the load fuse first. Routing signal and power wiring separately helps reduce electromagnetic interference.

Addressing, software and programming cable

The Y labels are local terminal numbers. As the first digital output expansion on a DVP-SS2, Y0–Y7 map to Y20–Y27 and Y10–Y17 map to Y30–Y37. Preceding modules can change the assigned PLC addresses. Connect the unit to the compatible CPU's expansion bus and check the Y addresses in the ladder program.

Use WPLSoft or ISPSoft to load the program into the supported host CPU. For the DVP-SS2 COM1 RS-232 port, use UC-PRG020-12A for USB or UC-MS020-01A for a native PC serial port. Install the USB cable driver and select the assigned COM number. Configure the COMMGR channel for ISPSoft.

Related models

DVP16SN11TS has 16 PNP sourcing outputs. DVP08SN11T has eight NPN transistor outputs and DVP08SN11R has eight relay outputs. DVP16SP11T has eight inputs and eight NPN outputs. DVP32SN11TN has 32 transistor outputs and uses its own channel ratings and common terminal arrangement.

Editor's Note

On a used module, check the 11T suffix and the UP, ZP0 and ZP1 markings. Inspect the terminal blocks and expansion connector for damage.

If an entire group stays off, use a multimeter to check for 24 V DC between UP and that group's ZP terminal.

Isolate the machine loads and check Y0–Y7 and Y10–Y17 one at a time with a small fused DC test load. Check that the load follows the command as well as the LED.

If a load stays on after the command clears, check the field wiring for a short circuit. Compare the channel's behavior with a known good test load.

Back up the CPU program and record the Y addresses before replacement. Recheck each group's simultaneous load current at the cabinet temperature.

Related topics

Delta PLC · Delta DVP series · Expansion modules · PLC input and output modules · Delta DVP PLC PDF files · Second-hand Delta equipment