Delta DVP06PT-S
Delta DVP06PT-S 6-Channel RTD Temperature Module
The Delta DVP06PT-S is a temperature input module that adds six individually configurable RTD channels to a DVP Slim PLC. It reads two- or three-wire resistance temperature sensors directly. Typical applications include monitoring dryers, heating zones and tanks from the PLC and HMI.
See Delta DVP PLC files for the terminal diagram, sensor curves and control registers.
Sensor types and measuring ranges
The rated range is −180 to +800 °C for Pt100 and Pt1000, −80 to +170 °C for Ni100 and Ni1000, −60 to +200 °C for LG-Ni1000, and −50 to +150 °C for Cu50 and Cu100. The Pt100 and Pt1000 modes use a 3850 ppm/°C curve. Check the probe’s own limits when choosing the operating range.
Module firmware V4.12 or later supports the 0–300 Ω and 0–3000 Ω resistance modes. Celsius resolution is 0.1 °C, and Delta specifies a response time of 160 ms per channel. Connect 24 V DC (20.4–28.8 V DC) to the module’s supply terminals. Power consumption is up to 2 W.
RTD wiring and field applications
Each channel has L+, L− and I− terminals. Connect a two-wire probe to L+ and L− and jumper L− to I−. For a three-wire probe, connect the two leads from the same end of the element to L− and I−, and the third lead to L+. Three-wire wiring compensates for lead resistance when the leads have matching resistance.
When replacing a temperature sensor, check the probe label for the sensor type and wire count. In a two-wire circuit, lead resistance can introduce an offset, especially with Pt100. For type K or J thermocouples, select a thermocouple input module such as the DVP04TC-S. In heating zones, the measurement can serve as feedback for PID control in the PLC.
PLC compatibility, programming and registers
Fit the module to the right-side bus of a compatible DVP Slim CPU. Check the host’s special-module capacity in DVP-SS2, DVP-SA2, DVP-SX2 and DVP-SV2 projects. The special module closest to the CPU is numbered K0. Read measurements from its special-module registers.
Use TO to write settings and FROM to read measurements in the CPU-supported WPLSoft or ISPSoft. For example, use an UC-PRG020-12A cable on the CPU’s COM1 RS-232 port for the DVP14SS211R. See DVP programming cables for other CPU connections.
CR#0 holds the model code (H’CA) and CR#34 holds the firmware version. CR#1 selects modes for CH1–CH4, and CR#31 handles CH5–CH6. CR#2 sets shared averaging for all channels (K1–K20, factory default K10). CR#6–11 hold average readings, CR#18–23 hold current Celsius or resistance readings, and CR#30 reports errors.
Reading example. In CH1 temperature mode, 253 from CR#18 represents 25.3 °C. Treat the value as a signed 16-bit number in the PLC or HMI and use one decimal place for Celsius.
Editor’s Note
Start with the label on a used module. Verify DVP06PT-S and inspect the six channel terminals, side-bus socket and supply terminal.
Check one channel against a reference. Use a known RTD or RTD simulator on the bench. Select the correct sensor mode, then compare the raw reading with the displayed temperature.
Test channels five and six separately. CH5–CH6 use a different setup register, so they can retain an incorrect mode even when the first four channels read correctly.
Check the wiring if readings show a fixed offset. On a two-wire circuit, check the jumper. On a three-wire circuit, identify the two same-end leads with an ohmmeter with the power switched off. Read CR#30 if the ERR LED lights.
Distinguish display resolution and accuracy. A 0.1 °C display increment is the resolution. When process tolerance matters, use a reference to check measurement accuracy with the probe, cable and module connected together.