Delta DVP04PT-S — 4-channel Pt100 / RTD temperature input module

The Delta DVP04PT-S adds four resistance temperature inputs to compatible Delta DVP PLCs. This Slim temperature module converts readings from CH1–CH4 into signed values the PLC can read. Typical Pt100 applications include extruder heating zones, hot-water circuits and machine moulds.

Choose the RTD element, cable and mounting together. A bayonet Pt100 can fit into a mould, while a head-mounted Pt100 provides a termination point for field wiring. An RTD input measures resistance. A thermocouple input measures the voltage generated by the sensor. See the Pt100 and thermocouple comparison for selection. If the cabinet receives 4–20 mA from a Pt100 transmitter, connect it to a suitable current input.

Sensor types, supply and wiring

Delta’s current manual specifies a 24 V DC supply (20.4–28.8 V DC), 0.1 °C resolution and a response time of 200 ms per channel. It lists Pt100, Pt1000, Ni100, Ni1000, LG-Ni1000, Cu50 and Cu100. The rated Pt100 and Pt1000 measuring range is −180 to +800 °C. Check the probe’s own limits to determine the usable range. Measurement accuracy and 0.1 °C resolution are separate specifications.

Firmware check. Delta’s 2004 DVP04PT-S sheet describes three-wire Pt100 wiring. The current manual shows two- and three-wire RTD wiring and additional sensor modes. On a used unit, read the firmware version from CR#34 and check the terminal markings against the drawing for that unit. Delta specifies V4.16 or later for the 0–300 Ω and 0–3000 Ω resistance modes.

In the current manual’s three-wire diagram, the two leads from the same end of the element go to L− and I−. The single lead goes to L+. The two-wire diagram shows a jumper between L− and I−. Three-wire wiring helps compensate for lead resistance. Route the probe cable away from motor and drive power wiring.

PLC programming, registers and Modbus

PLC programming takes place on the host CPU. Use WPLSoft or ISPSoft according to CPU support. For a compatible 8-pin RS-232 CPU port, see the UC-PRG020-12A and other DVP programming cables. Use FROM to read registers and TO to write them over the expansion connection. The special module closest to the CPU is numbered 0.

In normal measuring mode, CR#6–9 hold average °C for CH1–CH4 and CR#18–21 hold current °C. CR#12–15 hold average °F and CR#24–27 hold current °F. With this module first in the special module chain, FROM K0 K18 D100 K4 reads the four current °C values into D100–D103. Read them as signed values. 253 = 25.3 °C and −54 = −5.4 °C. In the current manual, CR#1 sets sensor mode, CR#2–5 set channel averaging and CR#30 reports errors.

For standalone RS-485 use, check the model’s Modbus RTU or ASCII settings. In normal measuring mode the CH1 average °C register is 0x406A and the current °C register is 0x4076. Use read function 03. For a client that expects one-based decimal addresses, enter 16491 and 16503. Delta’s connection note states that the module’s RS-485 port is disabled when the module is attached to a CPU through the side expansion bus. On supported firmware, enabling PID mode changes the register map.

Editor’s Note

When buying used, check the DVP04PT-S nameplate, removable terminals and side expansion connector.

With power off, use a multimeter to find the two leads from the same end of a three-wire probe. There should be low resistance between them. Check the colours against the probe’s own wiring diagram.

Bench-test each channel using a known-good three-wire Pt100 or RTD simulator. If one channel reads significantly differently on the same reference, check its terminals and sensor mode.

If the reading jumps, check the probe leads and connections first. A larger averaging count steadies the reading and slows its response to changes in temperature.

If the HMI shows 253 for 25.3 °C, check the decimal setting. Test below zero to confirm that the PLC and HMI read the value as signed.