Delta AS04RTD-A 4-Channel RTD Temperature Input Module
The Delta AS04RTD-A is a four-channel input module for 2- or 3-wire RTDs on Delta AS PLCs. It converts resistance changes from temperature sensors into values the PLC can read. A Pt100 probe can be used to monitor tank, mould or bearing temperature. The unit belongs to the Delta AS analog and measurement module family.
Sensor types and measurement specifications
Supported sensors include Pt100, Pt1000, JPt100, Ni100, Ni1000, LG-Ni1000, Cu50 and Cu100. Ni120 requires module firmware V1.06 or later. Resistance ranges are 0–300 Ω and 0–3,000 Ω. The supply is 24 VDC (20.4–28.8 VDC), with 0.1 °C temperature resolution and a conversion time of 200 ms per channel. Delta specifies a rated input range of −180 to +800 °C for Pt100 and Pt1000. Check the probe’s own temperature limits for the application.
Wiring and PLC configuration
For a two-wire probe on CH1, connect the sensor to L1+ and L1− and jumper L1− to I1−. For a three-wire probe, connect the two leads from the same end of the sensing element to L1− and I1−. Connect the third lead to L1+. Use the corresponding terminal numbers for the other channels. Route shielded sensor cable away from power wiring.
In a compatible AS200 or AS300 project, add the module in HWCONFIG in ISPSoft. Select the sensor type for each channel. Check the measurement units, averaging filter and sensor disconnection settings. Go online through COMMGR and verify the channel readings and project data addresses.
Related modules
Use the AS06RTD-A for six RTD inputs. Choose the module based on the difference between Pt100 and thermocouple signals. The AS04TC-A provides four thermocouple inputs and the AS08TC-A provides eight. For a temperature transmitter with a 4–20 mA output, consider an analog current input such as the AS04AD-A.
Editor’s Note
When buying used, inspect the removable terminal block and side connector.
If the project uses Ni120, read the module’s firmware version on the bench.
For long runs, use a three-wire probe with matched lead resistance to compensate for the cable.
If readings are consistently high, check two-wire lead resistance and the channel’s sensor setting.
At commissioning, test each input with a suitable RTD simulator and check the sensor-break alarm.