Delta AS06RTD-A

Delta AS06RTD-A 6-Channel RTD Temperature Module

Delta AS06RTD-A is a Delta AS PLC analog measurement module with six channels for two- or three-wire RTDs. This AS expansion module reports 16-bit temperature data with a resolution of 0.1 °C or 0.1 °F and a conversion time of 200 ms per channel.

Sensor Types and Measurement Ranges

Supported RTDs include Pt100, Pt1000, JPt100, Ni100, Ni1000, LG-Ni1000, Cu50 and Cu100. Ni120 requires module firmware V1.06 or later. Resistance measurement ranges are 0–300 Ω and 0–3000 Ω. Delta specifies a rated range of −180 to +800 °C for Pt100 and Pt1000. Check the probe’s temperature limits and tolerance class for the application.

Two- and Three-Wire RTD Connections

For a two-wire sensor, Delta’s diagram shows a jumper between the relevant channel’s Ln− and In− terminals. On the module, I12−, I34− and I56− are the paired In− terminals. Trace the channel in the wiring diagram before connecting it. With three-wire RTDs, leads of the same length and cross-section help reduce lead resistance error. Route shielded sensor cable separately from drive and motor wiring. Connect the external 24 V DC supply to the module’s power terminals.

ISPSoft Configuration and Data Reading

Add the module in its physical installation order in the AS200 or AS300 project under the Delta AS PLC family. In HWCONFIG in ISPSoft, select the sensor type for each channel and choose °C or °F. Connect through COMMGR to monitor channel readings and error status. Temperature readings are in tenths of a degree. In Celsius mode, 253 represents 25.3 °C. See the Delta PLC and HMI manuals for hardware and project settings.

Editor’s Note

Before buying a used module, inspect the 06RTD label, terminals and side connector.
Check the Pt100 or Pt1000 selection in the project before testing.
Use a known RTD or calibrator to test all six channels in turn.
If the leads on a three-wire probe show different resistances, inspect the cable and splices.
If a reading stays at a range limit, check sensor continuity, channel status and supply together.

Related Topics

See AS04RTD-A for four RTD channels, and AS04TC-A or AS08TC-A for thermocouples. Read the Pt100 and thermocouple comparison when selecting a sensor. For voltage and current signals, see AS08AD-B and AS06XA-A.

Delta PLC accessories · Delta PLC models · Second-hand Delta automation

External references · Delta AS Module Manual, chapter 6 (English) · AS04RTD-A / AS06RTD-A instruction sheet (includes English and Turkish).