Delta AS08TC-A

Delta AS08TC-A 8-channel thermocouple input module

The Delta AS08TC-A adds eight temperature measurement channels to a Delta AS PLC system. This Delta AS measurement module reads individual temperature zones in ovens, dryers and other multi-zone heating equipment.

Thermocouple types, resolution and wiring

Standard thermocouple types are J, K, R, S, T, E, N and B. The module manual also lists C, U, L and TXK. Check the installed firmware and HWCONFIG channel options for these types. A ±100 mV mode is available for analog voltage inputs. Use an RTD module for Pt100 measurements.

The module uses a 24-bit A/D converter. Temperature resolution is 0.1 °C / 0.1 °F, with a conversion time of 200 ms per channel. Delta specifies overall accuracy of ±0.5% of full scale at an ambient temperature of 25 °C. The module takes 24 V DC power within 20.4–28.8 V DC. Match the probe’s positive and negative leads to the correct channel on the removable terminal block.

ISPSoft, channel setup and programming cable

In HWCONFIG in ISPSoft, place the AS08TC-A in its physical module position. Check each channel’s sensor type, averaging and sensor disconnection alarm. The module-wide °C or °F setting is selected through CR#41. In Celsius mode, if the HMI reads integer temperature data, scale 250 to 25.0 °C. With floating-point data, the example value is already 25.0.

The PC connects through the AS CPU. Select the COMMGR channel for the port on the AS200 or AS300 CPU. Use a Mini USB data cable or an RJ45 Ethernet cable as supported by the CPU. See Delta PLC cables and PLC programming for connection details.

Editor’s Note

When buying used, ask for photos of the AS08TC-A label and removable terminal blocks.

Check the probe type, extension cable type and lead polarity together.

Set the correct thermocouple type before checking a channel against a known temperature.

If the reading fluctuates when a motor starts, check where the probe cable runs near motor wiring.

Test the open-sensor alarm and the HMI decimal display before commissioning.

Related topics

AS04TC-A (4 thermocouple inputs) · AS04RTD-A (4 RTD inputs) · AS06RTD-A (6 RTD inputs) · AS04AD-A and AS08AD-B (general-purpose analog inputs)

Delta PLC and HMI manuals · AS expansion modules · Delta PLC · Used Delta equipment

External references · AS Module Manual, Chapter 7 (EN) · AS04TC-A / AS08TC-A instruction sheet (TR/EN)