Delta AS04TC-A

Delta AS04TC-A four-channel thermocouple module

The Delta AS04TC-A is a four-channel thermocouple input module in the Delta AS analogue and measurement range. It sends temperature readings from ovens, extruders and heating zones to the PLC. It uses a 24 V DC supply and provides 0.1 °C / 0.1 °F resolution with 200 ms conversion time per channel.

Sensor types and measurement ranges

Select a thermocouple type or −100 to +100 mV input mode for each channel. Delta lists rated ranges of −100 to +1200 °C for type J and −100 to +1350 °C for type K. Other ranges are T −150 to +400 °C, E −150 to +980 °C, N −150 to +1300 °C, R/S 0 to 1750 °C and B 200 to 1800 °C.

The 2024 hardware manual also lists C, U, L and TXK. Check the module firmware and available project settings before selecting these types. See what a thermocouple is, thermocouple types and thermocouple standards for sensor selection.

Wiring and channel setup

Connect the thermocouple to the channel’s I+ and I− terminals with the correct polarity. Follow the wiring diagram for shield and SLD connections. Route the signal cable away from drive and heater power wiring. The module supply range is 20.4–28.8 V DC. See AS power supplies for supply selection.

For an AS200 or AS300 project, use HWCONFIG → Device Setting in ISPSoft to configure CH1–CH4. Check the temperature unit, averaging and sensor disconnection detection. Use the channel fault status alongside the temperature value in PLC alarms. See COMMGR for PC connection and Delta PLC software for other tools.

Related modules

For eight thermocouple inputs, see the AS08TC-A. The Pt100 and thermocouple comparison helps with sensor selection. See the AS04RTD-A or AS06RTD-A for Pt100 and other RTD inputs, or the AS04AD-A for standard voltage and current inputs.

Editor’s Note

On a used module, inspect the label and check that the removable terminal block fits securely.
Use a known thermocouple type or a thermocouple simulator for testing.
Try the same sensor on all four channels and compare the readings.
If the reading falls when the probe is warmed, start by checking polarity and the selected sensor type.
During a sensor disconnection test, verify both the channel diagnostic and the PLC alarm.

PDFs and related topics

See our Delta PLC and HMI manuals. Section 4.10.3 of the hardware manual covers wiring. Chapter 7 of the module manual covers channel settings and diagnostics.

AS expansion modules · Delta AS PLC series · Delta PLC · Used Delta products

External references · AS hardware manual (EN) · AS module manual (EN) · AS04TC-A / AS08TC-A installation sheet (TR/EN)